Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 40
]
Pr4 Group - Program 4
no. Param.
Description
Dec.
Point
Values
Default
237
P4.F
Program 4 - Action at power up
0
nonE
Programmer not used;
S.uP.d Start at power up with a first step in stand-by;
S.uP.S Start at power up;
u.diG
Start at Run command detection only;
u.dG.d Start at Run command with a first step in stand-by.
nonE
238
P4.u
Program 4 - Time unit of the soaks
2
hh.nn
Hours and minutes;
nn.SS Minutes and seconds.
hh.nn
239
P4.E
Program 4 - Instrument behaviour at the
end of the program execution
0
cnt Continue;
SPAt
Go to the set point selected by A.SP;
St.by
Go to stand-by mode.
A.SP
240
P4.nE
Program 4 - Number of executions
0
1... 99 times/inF indefinitely
241
P4.Et
Program 4 - Time of the end program
indication
2
0.00 (oFF)/0.01... 99.59 nn.ss/inF (steady ON)
oFF
242
P4.S1
Program 4 - Set point of the first soak
dP
From SPLL to SPHL
0
243
P4.G1
Program 4 - Gradient of the first ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
244
P4.t1
Program 4 - Time of the 1
st
soak
2
0.00... 99.59 Time unit of the soaks
0.10
245
P4.b1
Program 4 - Wait band of the 1
st
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
246
P4.E1
Program 4 - Events of the 1
st
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
247
P4.S2
Program 4 - Set point of the 2
nd
soak
dP
OFF or from SPLL to SPHL
0
248
P4.G2
Program 4 - Gradient of the 2
nd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
249
P4.t2
Program 4 - Time of the 2
nd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
250
P4.b2
Program 4 - Wait band of the 2
nd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
251
P4.E2
Program 4 - Events of the 2
nd
group
2
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
252
P4.S3
Program 4 - Set point of the 3
rd
soak
dP
OFF or from SPLL to SPHL
0
253
P4.G3
Program 4 - Gradient of the 3
rd
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
254
P4.t3
Program 4 - Time of the 3
rd
soak
2
0.00... 99.59 Time unit of the soaks
0.10
255
P4.b3
Program 4 - Wait band of the 3
rd
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
256
P4.E3
Program 4 - Events of the 3
rd
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
257
P4.S4
Program 4 - Set point of the 4
th
soak
dP
OFF or from SPLL to SPHL
0
258
P4.G4
Program 4 - Gradient of the 4
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
259
P4.t4
Program 4 - Time of the 4
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
260
P4.b4
Program 4 - Wait band of the 4
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
261
P4.E4
Program 4 - Events of the 4
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
262
P4.S5
Program 4 - Set point of the 5
th
soak
dP
OFF or from SPLL to SPHL
0
263
P4.G4
Program 4 - Gradient of the 5
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
264
P4.t5
Program 4 - Time of the 5
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
265
P4.b5
Program 4 - Wait band of the 5
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
266
P4.E5
Program 4 - Events of the 5
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00
267
P4.S6
Program 4 - Set point of the 6
th
soak
dP
OFF or from SPLL to SPHL
0
268
P4.G6
Program 4 - Gradient of the 6
th
ramp
1
0.1... 999.9 (E.U./minute)/inF = Step transfer
inF
269
P4.t6
Program 4 - Time of the 6
th
soak
2
0.00... 99.59 Time unit of the soaks
0.10
270
P4.b6
Program 4 - Wait band of the 6
th
soak
dP
0 (oFF)/1... 9999 (E.U.)
oFF
271
P4.E6
Program 4 - Events of the 6
th
group
0
00.00... 11.11 (
0
= event OFF;
1
= event ON)
00.00