Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 24
negative set point change).
3.
Setting [131] P1.E = St.by at program end the
instrument goes immediately in Stand-by mode
(control outputs go to OFF and the instrument
operate as an indicator).
[132] P1.nE - Execution number
Available:
When [129] P1.F is different from
nonE
.
Range:
1 to 99 executions;
inF Indefinitely.
Note:
Setting [132] P1.nE = inF the program execution will
be repeated until a reset command is detected.
[133] P1.Et - Time of the End program indication
Available:
When [129] P1.F is different from
nonE
.
Range:
oFF
Function not used;
00.01... 99.59 minutes and seconds;
inF
Indefinitely ON.
Note:
Setting [133] P1.Et = inF the end program indication
goes OFF only when a reset command or a new RUN
command is detected.
[134] P1.S1 - Set point of the first soak
Available:
When [129] P1.F is different from
nonE
or
[129] P1.F is different from S.uP.d.
Range:
From [75] SPLL to [76] SPHL.
[135] P1.G1 - Gradient of the first ramp
Available:
When [129] P1.F is different from
nonE
or
[129] P1.F is different from S.uP.d.
Range:
0.1... 999.9 engineering units per minute;
inF
Step transfer.
[136] P1.t1 - Time of the first soak
Available:
When [129] P1.F is different from
nonE
.
Range:
0.00... 99.59 Time units.
Note:
Setting a time equal to zero, the instrument uses the
wait band before to go to the next step.
[137] P1.b1 - Wait band of the first soak
Available:
When [129] P1.F is different from
nonE
or
[129] P1.F is different from S.uP.d.
Range:
OFF... 9999 engineering units.
Note:
The wait band suspends the time counting when
the measured value goes out of the defined band
(guaranteed soak).
Temperature
Wait
Wait
Soak x
Soak x
Ramp x + 1
Ramp x
Wait
Soak SP
Wait
SP
Measure
[138] P1.E1 - Events of the first group
Available:
When [129] Pr.F is different from
nonE
or
[129] Pr.F is different from S.UP.d.
Range:
00.00... 11.11 where:
0
event OFF;
1
event ON.
Event 1 status during ramp
Event 2 status during ramp
Event 1 status during soak
Event 2 status during soak
Display
Ramp
Soak
Event 1
Event 2
Event 1
Event 2
00.00
off
off
off
off
10.00
on
off
off
off
01.00
off
on
off
off
11.00
on
on
off
off
00.10
off
off
on
off
10.10
on
off
on
off
01.10
off
on
on
off
11.10
on
on
on
off
00.01
off
off
off
on
10.01
on
off
off
on
01.01
off
on
off
on
11.01
on
on
off
on
00.11
off
off
on
on
10.11
on
off
on
on
01.11
off
on
on
on
11.11
on
on
on
on
[139] P1.S2 - Set point of the second soak
Available:
When [129] P1.F is different from
nonE
Range:
From [75] SPLL to [76] SPHL;
oFF
Program end.
Note:
It is not necessary to configure all steps.
Using, for example, 2 groups only, it is sufficient to set
the set point of the third group equal to OFF.
The instrument will mask all the following parameters
of the program in editing.
[140] P1.G2 - Gradient of the second ramp
Available:
When [129] P1.F is different from
nonE
and
[139] P1.S2 is different from
oFF
.
Range:
0.1... 999.9 engineering units per minute;
inF
Step transfer.
[141] P1.t2 - Time of the second soak
Available:
When [129] P1.F is different from
nonE
and
[139] P1.S2 is different from
oFF
.
Range:
0.00... 99.59 time units.
Note:
Setting a time equal to zero, the instrument uses the
wait band before to go to the next step.
[142] P1.b2 - Wait band of the second soak
Available:
When [129] P1.F is different from
nonE
and
[139] P1.S2 is different from
oFF
.
Range:
OFF... 9999 engineering units.
Note:
For more details see [137]P1.b1 parameter.