PAn group - Operator HMI parameters
no. Param.
Description
Dec.
Point
Values
Default
86
PAS2
Level 2 password
(limited access level)
0
oFF Level 2 not protected by password);
1... 200
20
87
PAS3
Level 3 password (com-
plete configuration level) 0
3... 200
30
88
uSrb
button function dur-
ing RUN TIME
nonE No function;
tunE Auto-tune/auto-tune enabling. A single press (longer than 1 second)
starts the auto-tune;
oPLo Manual mode. The first pressure puts the instrument in manual mode (oPLo)
while a second one puts the instrument in Auto mode;
AAc Alarm reset;
ASi
Alarm acknowledge;
chSP Sequential set point selection;
St.by Stand by mode. The first press puts the instrument in stand by mode while
a second one puts the instrument in Auto mode.;
P.run Program run;
P.rES Program reset;
P.r.H.r Program run/hold/reset.
P.r.H.r
89
diSP
Display management
nonE Standard display;
Pou Output Power;
PoS Valve position (servomotor control);
SpF Final set point;
Spo Operative set point;
AL1 Alarm 1 threshold;
AL2 Alarm 2 threshold;
AL3 Alarm 3 threshold;
Pr.tu - During a soak, the instrument shows the soak elapsed time;
-
During a ramp the display shows the operative set point. At the end of
the program execution, the instrument will show “
P.End
” messages alter-
nately with the measured value;
-
When no program is running, the instrument shows the standard display;
Pr.td - During a soak, the instrument shows the soak remaining time (count down);
- During a ramp the display shows the operative set point. At the end of
the program execution, the instrument shows “
P.End
” messages alterna-
tely with the measured value;
-
When no program is running, the instrument shows the standard display;
P.t.tu When the programmer is running, the display shows the total elapsed
time. At the end of the program execution, the instrument shows “
p.End
”
messages alternately with the measured value;
P.t.td When the programmer is running, the display shows the total remaining
time (count down). At the end of the program execution, the instrument
shows “
P.End
” messages alternately with the measured value;
PErc Percent of the power output used during soft start (when the soft start
time is equal to infinite, the limit is ever active and it can be used also
when ON/OFF control is selected).
Pr.tu
90
di.cL
Display colour (*)
0 The display colour is used to show the actual deviation (PV - SP);
1 Display red (fix);
2 Display green (fix);
3 Display orange (fix).
0
91
AdE
Deviation for display
colour management (*)
1... 9999 (E.U.)
5
92
di.St
Display Timeout
2
oFF Display always ON
0.1... 99.59 (mm.ss)
oFF
93
fiLd
Filter on the displayed
value
1
oFF Filter disabled)
0.1... 20.0 (E.U.)
oFF
95
dSPu
Instrument status at
power ON
AS.Pr Starts in the same way it was prior to the power down;
Auto Starts in Auto mode;
oP.0 Starts in manual mode with a power output equal to zero;
St.bY Starts in stand-by mode.
AS.Pr
96
oPr.E
Operative modes
enabling
ALL All modes will be selectable by the next parameter;
Au.oP Auto and manual (
oPLo
) mode only will be selectable by the next pa-
rameter;
Au.Sb Auto and Stand-by modes only will be selectable by the next parameter.
ALL
97
oPEr
Operative mode selection
If oPr.E = ALL:
- Auto = Auto mode;
-
oPLo = Manual mode;
-
St.bY = Stand by mode.
If oPr.E = Au.oP: -
Auto = Auto mode;
- oPLo = Manual mode.
If oPr.E = Au.Sb: - Auto = Auto mode;
-
St.bY = Stand by mode.
Auto
*
Not available on those controllers with white display.