Ascon Tecnologic - KM5P Line - ENGINEERING MANUAL - PAG. 1
KM5P
CONTROLLER, PROGRAMMER
and SET POINT SETTER
Engineering Manual
21/11 - Code: ISTR_M_KM5P_E_00_--
Ascon Tecnologic S.r.l.
Viale Indipendenza 56, 27029 Vigevano (PV) - ITALY
Tel.:
+39 0381 69871/
FAX:
+39 0381 698730
www.ascontecnologic.com
e-mail:
1. OUTLINE DIMENSIONS (mm)
1.1 Mounting requirements
This instrument is intended for permanent installation, for
indoor use only, in an electrical panel which encloses the
rear housing, exposed terminals and wiring on the back.
Select a mounting location having the following characteristics:
1.
It should be easily accessible;
2.
There is minimum vibrations and no impact;
3.
There are no corrosive gases;
4.
There are no water or other fluids (i.e. condensation);
5.
The ambient temperature is in accordance with the
operative temperature (0... 50°C);
6.
The relative humidity is in accordance with the instrument
specifications (20... 85%);
The instrument can be mounted on panel with a maximum
thickness of 15 mm.
When the maximum front protection (IP65) is desired, the
optional gasket must be mounted (see “
How to order
”
paragraph for details).
1.2 Dimensions
1.2.1 Controller with non removable terminals
PV
AT
48 *
14
11
48
48
*
The controllers with universal power supply,
have the body long 63.3 mm
1.2.2 Removable terminals
40
15.5
18.85
26
15
8.3
40
8.3
Screw removable terminals
Spring removable terminals
1.2.3 Panel cutout
45
+0.6
65 mm min.
65 mm min.
45
+0.6
2. ELECTRICAL CONECTIONS
2.1 Wiring diagram
L
RS485
Thermo-
couple
DI1
OP3
OP2
OP1
OP4
(note)
DI2 (note)
Analogue input
mV, V
mA
Note:
Terminal 4 can be programmed as:
- Digital Input
(DI2) connecting a dry contact
between terminals 4 and 16;
- 0... 12 V SSR Drive Output
(OP4) connecting
the load between terminals 4 and 16;
- 12 Vdc (20 mA) transmitter power supply
connecting the 2 wire transmitter between
terminals 4 and 1; for 3 wire transmitter connect
terminal 4 to transmitter power supply input
and terminal 1 and 2 to transmitter signal output.
12 VDC
(note)
PV
4... 20 mA
3 wire transmitter
12 VDC
(note)
PV
Pt100
Pt1000/NTC/PTC
4... 20 mA
2 wire transmitter
Neutral
Power
supply
Line
open
close
TERMINALS
Pin connector
q
1.4 mm max.
(0.055 in.)
Stripped wire
L:
5.5 mm
(0.21 in.)
General notes about wiring
1.
Do not run input wires together with power cables.
2.
External components (like zener barriers, etc.) connected
between sensor and input terminals may cause errors in
measurement due to excessive and/or not balanced line
resistance or possible leakage currents.
3.
When a shielded cable is used, it should be connected at
one point only.
4.
Pay attention to the line resistance; a high line resistance
may cause measurement errors.