Installation, Operation and Maintenance Manual
【
H-A077-E-00
】
3-Way Ball valve Type 23 Electric actuated Type Z 15
~
50mm (½”-2”)
8
7. Specifications of actuator
List of specifications
Actuator type
AV-Z-025
Rated torque
*1.
10 N-m
Maximum output torque
25 N-m
Rated voltage
*2.
95
~
240VAC ± 10%
50/60Hz (Universal power supply)
Power consumption
17VA
Motor protection
*3.
Overcurrent protection element
Operating range (Min-Max)
0°
~
90°
(
Maximum operating angle 110°: -10°
~
100°
)
Opening and closing time
8 sec. / 90° (No load), 9 sec. / 90° (Loaded)
External dimensions
W175(145)×D120×H150mm
*(145) Excluding cable gland
Weight
1.7kg
Usage
environment
Installation
environment
*4.
Indoor and outdoor (with restrictions and conditions)
Protection class
IP67
Pollution level
2
Ambient
temperature
-10
~
55
°
C (There should be no freezing or condensation)
Duty cycle
*1.
30%
Wiring port
Cable gland
For power input &signal output: 1 place each, CE / VDE standard
Terminal block
Screw type, Applicable wire:
Outer diameter
φ
7
~
13mm, Wire diameter 0.75
~
2.0mm
2
Housing material
Cover: Polycarbonate (blue) flame retardant UL94V-0
Body: Polycarbonate with glass (black) flame retardant UL94V-0
Function
State output
*5.
Left open & Right open output: 1 place each (Non-voltage contacts),
Contact capacity: Max. 250VAC–1A
Status display
Indicator / LED Lamp (Green: Left open, Red: Right open)
Manual operation
With Auto/Manual changeover switch.
9 rotations / 90° with a Allen wrench
Space heater
Rated output: 5W
*
It works only when the power is on.
Insulation resistance
500VDC, 10M
Ω
or more
Withstand voltage
1500VAC , 1 minuite
(Note)
*1.
The load and duty cycle conform to S4 (see IEC60034-1), which is equivalent to the valve load.
*2.
As a guide, the length of the power cable should be within 100 meters.
*3.
In the event of an overload, the thermistor will function and the power to the motor will be cut off.
(It will self-recover when the power supply is cut off.)
*4.
This actuator can be used in an IP67 environment, but when opening the housing for maintenance
or adjustment, do so in a pollution level 2 environment (for example, indoors and other dust-free
and moisture-free environments).
*5. Keep the equipment connected to the limit switch (non-voltage contact) for the left open / right
open signal within the contact capacity (1A). (May be damaged)