Array electronic TC-Pro482CRA User Manual Download Page 56

Comparison Table

Summary of Contents for TC-Pro482CRA

Page 1: ...Ver 3 0...

Page 2: ...tage input Finger safe terminals screw terminal block models Three language instruction manual Applied to connect PC HMI Contents Model Number Structure 2 Speci cations 3 Nomenclature 6 Operating Proc...

Page 3: ...connector 1 5m Cable CAB 090A485 9 pin Female D sub cable for RS 422 connector 1 5m Cable CAB 090A422 9 pin male D sub adapter for CAB 090A232 CAB 090A485 CAB 090A422 ADP 090401 9 pin Female D sub cab...

Page 4: ...ge 3V max OFF impedance 100k min Voltage Input High logic level 4 5 to 30 VDC Low logic level 0 to 2 VDC Input resistance approx 4 7 k Signal Reset Gate Minimum input signal width 1 or 20 ms selectabl...

Page 5: ...k Reset input Minimum input signal width 1 20 ms selectable same settingfor all inputs Reset system External manual and automatic reset internal according to C R P and Q mode operation Output modes N...

Page 6: ...0 operations min 5 A at 250 VAC resistance load EMC EMI Emission Enclosure Emission AC mains EMS Immunity ESD Immunity RF interference Immunity Conducted Disturbance Immunity Burst Immunity Surge Immu...

Page 7: ...ue character height 9 mm Time Unit Display If the time range is 0 min 0 0 min 0 h 0 0 h 0h0 min this display flashes to indicate timing operation Set Value character height 4 mm The First Setting Key...

Page 8: ...Control output OUT Outputs take place according to designated operating mode when timer reaches corresponding set value Note Two control outputs can be used I O Functions 2 Stage Timer Inputs Start s...

Page 9: ...sets the total count value Hold the total count value at 0 during total reset input When used as a batch counter Reset the batch count value and batch output OUT1 Holds the batch count value at 0 duri...

Page 10: ...on page 23 Timer setting mode See Run Mode on page 12 Twin Timer setting mode See Run Mode on page 15 Twin Forecast setting mode See Run Mode on page 17 1 stage counter setting mode See Run Mode on p...

Page 11: ...dress Communication on off Set the transmision speed with key Set the parity check with key Set the date bit with key Set the stop bit with key Set the Station address HEX with key Set communication o...

Page 12: ...the key protection level KP1 to KP 5 The key protection indicator is lit while the key protection switch is set to ON See note 3s min See note 3s min K P ON Setting mode K P OFF Setting mode Run Mode...

Page 13: ...tput mode Output time Input signal width NPN PNP input mode K P level Set the time range with key Set the time mode with key Set the output mode with key Set the input signal width with key Set the NP...

Page 14: ...mode Z The present value is displayed in the main display and the ON duty ratio is displayed in the sub display A and Range light at the same time Set the ON duty ratio used in ON OFF duty adjustable...

Page 15: ...e selected output mode A A 1 A 2 A 3 b or b 1 If the output time is set to 0000 00s hold is displayed and the output is held Input signal width iflt Set the minimum signal input width 20ms or 1ms for...

Page 16: ...y Set Value Twin timer function setting mode KP 1 KP 2 KP 3 KP 4 KP 5 NPN input PNP input 20ms 1ms flicker OFF start flicker ON start Elapsed time Remaining time Set the K P level with key Set the NPN...

Page 17: ...ge to be timed in the range 000 000s to 999999h ON Time range timr Set the range to be timed in the range 000 000s to 999999h Timer Mode timm Set either the elapsed time UP or remaining time DOWN mode...

Page 18: ...olute Value with key Forecast value Absolute value Set time range with key for details refer to time range list Set the output mode with key A F 1 Set the input signal width with key 20ms 1ms Set the...

Page 19: ...value Set value Present value Forecast set value Set set value with the corresponding keys Set forecast set value with the corresponding keys When the absolute value is selected Present value Set val...

Page 20: ...to prevent setting error by prohibiting the use of certain operation keys by specifying K P level KP 1 to KP 5 For details refer to Key Protection Setting Mode on page 11 Forecast value Setting Exampl...

Page 21: ...modes other than K 2 D L and H only UP DOWN UP DOWN A UP DOWN B UP DOWN C Note Displayed only when the output mode is C R K 1 P Q A or K 2 000 001s 000 005s 099 990s 999 999s 000 001 001 000 999 999 S...

Page 22: ...the output mode If the output time is set to 0 00 HOLD is displayed and outputs are held HOLD can not be set when the output mode is K 2 Counting speed cnts Set the maximum counting speed 30Hz 5KHz fo...

Page 23: ...ount calculating mode is SUB Dual count set value Set dual count set value When the dual count value reaches the dual count set value signals are output according to the specified output mode CP1 CP2...

Page 24: ...is reset measured value initialized and output turned OFF on returning to run mode The characters displayed in reverse video are the initial values Set each setting item with the Key 30Hz 10KHz no dec...

Page 25: ...ut chattering can be prevented using average processing simple averaging Average processing can be set to one of four levels no average processing 2 times i e the average of 2 measurement values 4 tim...

Page 26: ...the keys Measurement value Measurement value OUT1 set value Measurement value OUT2 set value Displays the currently measured value OUT1 OUT2 set value Set OUT1 set value and OUT2 set value The measur...

Page 27: ...starts when the power comes ON or when the reset input goes OFF The control output is controlled using a sustained or one shot time period Timing Power Start signal input Output Basic Operation Output...

Page 28: ...set time is too short Set the value to at least 100ms contact output type Start signal input is disabled during timing Output mode b 1 Repeat cycle 2 timer does not reset when power comes ON Timing s...

Page 29: ...the power is OFF A sustained control output is used Timing Timing Sustained Power Start signal input Output Basic Operation Output is instantaneous when setting is 0 Z mode ON OFF duty adjustable flic...

Page 30: ...possible if the ON OFF time is too short Set the value to at least 100ms contact output type Start signal input is disabled during timing Output Mode ton flicker ON start Timing starts when the start...

Page 31: ...peration The names in parentheses are used for the absolute value setting Output is instantaneous when the set value is 0 Start signal input is disabled during timing F 1 Mode Cumulative Timer does no...

Page 32: ...vidual input mode UP DOWN C Quadrature input mode Note If the configuration selection is set to dual count CP1 and CP2 input will operate in the same way as the count input CP1 of UP increment mode Th...

Page 33: ...e p e a t o n e s h o t operation OUT1 self holding output turns OFF after the OUT2 o n e s h o t o u t p u t time The OUT1 one s h o t o u t p u t t i m e is independent of OUT2 R The present value d...

Page 34: ...present value c o n t i n u e s t o increase decrease for the one shot output time but returns to the reset start status after the one shot output time has elapsed The outputs repeat one shot operati...

Page 35: ...nderflow value is reached OUT1 is held while the present value is less than or equal to set value 1 OUT2 is held while the present value is less than or equal to set value 2 H The display continues to...

Page 36: ...ber of times the count value returns to 0 when it reaches the full scale limit The batch counter continues after count completion Batch output is held until batch counter reset is input When the batch...

Page 37: ...CP1 or CP2 input Note Counting is not possible for CP1 during reset 1 input CP2 will not be affected The dual count value will be calculated based on a CP1 present value of 0 Counting is not possible...

Page 38: ...e OUT2 set value OUT set value Measurement value OUT2 set value OUT1 set value OUT2 set value Measurement value OUT2 set value Measurement value OUT1 set value OUT2 set value Measurement value OUT1 se...

Page 39: ...d Dimensions without Flush Mounting Adapter Note M3 terminal screw effective length 8mm Dimensions with Flush Mounting Adapter Panel Cutouts Note The mounting panel thickness should be 1 5 mm To allow...

Page 40: ...er Tachometer Dimensions Note all units are in millimeters unless otherwise indicated Dimensions without DIN Track Mounting Adapter Note M3 terminal screw effective length 8mm Dimensions without DIN T...

Page 41: ...090B order separately Waterproof Packing Flush Mounting Adapter End Plate CABC 44 Mounting Track PR 43 BK 6 0F A order separately ADP 090401 apdater changing 4 into 9 PIN Panel Protective Cover Commun...

Page 42: ...s connection to a voltage output sensor Gate CP1 Reset 2 Reset 1 Signal CP2 External voltage External voltage When SW is pressed the transistor is ON that shows the input has response Contact Input Ga...

Page 43: ...ansistor Connection to NPN open collector output sensor Gate CP1 Reset 2 Reset 1 Signal CP2 External voltage External voltage When SW is pressed the transistor is ON that shows the input has response...

Page 44: ...ception is possible unstable or impossible Turn the power ON and OFF using a relay with a rated capacity of 10A minimum to prevent contact deterioration due to inrush current caused by turning the pow...

Page 45: ...nal circuit from water penetration through the space between the TC Pro and operating panel attach a waterproof packing between TC Pro and installation panel and secure the waterproof packing with the...

Page 46: ...s min PV OFF set time PV ON set time Function setting mode OFF time range ON time range Timer mode ON OFF start mode Input signal width NPN PNP input mode Key protection level Note For details on the...

Page 47: ...h Decimal point position Prescale value NPN PNP input mode Key protection level Parity check Transmission speed Power ON Run mode Function setting mode Communication setting mode Present value set val...

Page 48: ...lue OUT2 set value Tachometer output mode Counting speed Decimal point position Prescale value Average processing Auto zero time Startup time Key protection level NPN PNP input mode Communication sett...

Page 49: ...99999 Time range min 000000 min 0000 00 9999 59 Time range h min 0000 00 h min 00000 0 99999 9 Time range h 00000 0 h 000000 999999 Time range h 000000 h 000 000 999 999 Time range s 000 000 s Present...

Page 50: ...0 s 0000 00 9999 59 Time range min s 0000 00 min s 00000 0 99999 9 Time range min 00000 0 min 000000 999999 Time range min 000000 min 0000 00 9999 59 Time range h min 0000 00 h min 00000 0 99999 9 Tim...

Page 51: ...esent setting value Same as the present value of the set value above Same as left Same as left Present value Same as the present value of the set value above Same as left Same as left absolute value s...

Page 52: ...ri none odd even none Date bit data 8bit 7bit 8bit bits Stop bit stop 1bit sbit 1bit bit Station address Hex addr 01 to ff 01 Communication OFF cosh on off on 1 stage Counter 2 Stage Counter Total Cou...

Page 53: ...99999 See note 1 Total and preset counter Parameter name parameter Setting range Default value Unit Set value Screen 1 Present value 99999 999999 000000 Set value 1 000000 999999 For conditions other...

Page 54: ...ion setting mode Parameter name parameter Setting range Default value Unit Set value Input mode cntm up down ud a ud b ud c See note 1 up Dual count calculating mode caln add sub See note 1 add Output...

Page 55: ...value 000000 999999 000000 000000 999999 000000 Function setting mode Parameter name parameter Setting range Default value Unit Set value Tachometer output mode totm hilo area hihi lolo hilo Counting...

Page 56: ...Comparison Table...

Reviews: