installation &
operating instructions
Design Envelope
4300
&
4380
Vertical In-line Pumping Unit
17
3.2
BACnet
ip & ms/tp
name
value range
description
DO004
1
= Hand mode
Pump in Hand mode
DO005
1
= off
Pump is off
DO006
1
= auto
Pump is in automatic mode
DO034
0
= stopped,
1
= running
Run feedback
DO068
0
= ok,
1
= alarm
Pump alarm
DO078
0
= ok,
1
= alarm
Run feedback alarm
DO088
0
= ok,
1
= alarm
Pump drive fault
DI151
Set pump to hand mode
DI152
Set pump to off
DI153
Set pump to auto mode
AO040
0-1000 (0%-100%)
Pump speed
AO053
0-10000 (0-1000.0)
amps
Pump drive current
AO054
0-10000 (0-1000.0)
VAC
Pump drive AC voltage
AO055
0-10000 (0-1000.0)
kW
Pump drive power
AO056
0-1000 (0.0-100.0) %
Pump drive speed feedback
AO093
0-32767 (0.0-3276.7)
Pump head
AI138
0-1000 (0.0-100.0) %
Pump hand speed
AI150
0-9999 (0.0-999.9)
Design head
AI151
0-9999 (0.0-999.9)
Zero flow head
AO1003
0-32767
Pump flow
AO1014
0-999
hours
Pump operating run hours
AO1015
0-32000
hours
* 1000
Pump operating run Khours
AO1050
0-32767 (0-327670)
Flow design