ROOF
Pa
ra
pe
t
W
all
If Air intake is below
Parapet wall. Air intake
must be Min. 10'
(3m)
away
3/4"=1'
Reference dimensions are ± 10%
All dimensions are ± 1"
Custom
Dwg No.
Customer / Job name:
Scale:
Description:
Drawn/
Revised by:
Checked/
Apv. by:
Revision:
MM/DD/YY
Date:
1/4" per ft. slope to appliance
All horizontal runs must be
supported every 24"
Air intake
90º Elbow w/
Bird Screen
Exhaust w/
Coupler &
Bird Screen
24"
(609mm)
or
12"
(305mm)
above
Maximum snow level
whichever is greater
18"
min. (257mm)
24"
max. (609mm)
8"
min. (203mm)
Recommended Drain
Fitting Before Vertical Run
Min. 12"
(305mm)
above Parapet wall
if wining 10' of wall
All horizontal runs must
be supported every 24
"
Exterior wall
Intake
Exhaust
18" Minimum (457mm)
24" Maximum (609mm)
24" (609mm or
12" (305mm) above
maximum snow level
whichever is greater
Right Side View
SHOWN OFFSET
FOR CLARITY
1/4" ft. slope to appliance
Front Elevation
8"
min.
(303mm)
18" min. (457mm)
24" max. (609mm)
Front Elevation
(Multiple Vents)
8"
min.
203 (mm)
18" min. (457mm)
24" max. (609mm)
- OR -
VENTING FOR MULTIPLE UNITS
,
with vents all on same horizontal plane,
spaced at least 8 inches apart, and at
level of highest unit.
NOTE: Exhaust must not terminate beneath an overhang!
**IMPORTANT NOTE: All vent pipes must be glued, properly supported and the
exhaust must be pitched a minimum of a 1/4" per foot back to the heater (to
allow drainage of condensate). All stainless venting must be sealed at each joint
per manufacturer’s instructions.
**IMPORTANT NOTE: All vent pipes must be glued, properly
supported and the exhaust must be pitched a minimum of a 1/4"
per foot back to the heater (to allow drainage of condensate). All
stainless venting must be sealed at each joint per manufacturer’s
instructions.
Figure 4.2 - Sidewall Vent With Down Elbow (Intake) & Up Elbow (Exhaust)
Figure 4.3 - Vertical Vent With Double Elbow (Intake) & Coupling (Exhaust)
,
NOTE: Intake must take into account any parapet walls.