Condensate Trap Cleaning Instructions
The condensate trap and entire drain system attached to it (above the neutralizer) should be cleaned at least once every year.
1. Turn off the power to the ABH.
2. Place a bucket under the condensate trap. Use caution when removing the
clean-out cap, as the trap is full of condensate and it may be hot.
3. Remove the condensate clean-out cap, and be sure the bucket is under the
open drain trap assembly to catch the debris and water.
4. Rinse out the clean-out cap in a sink to remove any dirt or buildup that may
have accumulated.
Maintenance - continued
5. Condensate drain assembly should now be checked for non-restricted flow throughout the entire assembly.
6. Reinstall the clean-out cap on the condensate trap.
7. Turn on the power to the ABH.
8. Make sure the hose from the condensate trap is not submerged too far into the neutralizer, there should be an air gap between
the highest level of condensate and the outlet hose from the trap.
9. Monitor the condensate drain until flow has been established.Monitor the condensate drain until flow has been established.