MAGS1 User Guide
19
V1.5 22-1-2016
4.16. Factory Settings
To enter this section, it is necessary to enter the Factory Password.
Modbus
register
Modbus
address
No. of
bytes
Data
type
No. of
decimal
Min
Value
Max Value
Default
Description
Read/
Write
4014
4013
4
Longint
0
0
1 000
-
Diameter
R/W
4016
4015
4
Longint
0
0
999999
-
Unit No.
R/W
4018
4017
4
Longint
3
0
36 000 000
-
Flow Qn
R/W
4020
4019
4
Longint
3
0
36 000 000
-
Calibration
Point 1
R/W
4026
4025
4
Longint
0
-
8388608
8388607
-
Calibration
Data 1
R/W
4022
4021
4
Longint
3
0
36 000 000
-
Calibration
Point 2
R/W
4028
4027
4
Longint
0
-
8388608
8388607
-
Calibration
Data 2
R/W
4024
4023
4
Longint
3
0
36 000 000
-
Calibration
Point 3
R/W
4030
4029
4
Longint
0
-
8388608
8388607
-
Calibration
Data 3
R/W
4032
4031
4
Bool
-
0
1
0
Zero Flow Set
R/W
4036
4035
4
Longint
7
0
1000000
0
Zero Flow
Constant
R/W
4034
4033
4
Bool
-
0
1
0
Zero Flow
Erase
R/W
4038
4037
4
Longint
-
0
1
1
Excitation
frequency,
0=3,125 Hz,
1=6,25 Hz,
R/W
4040
4039
4
Bool
-
0
1
1
Excitation,
0=ON,
1=OFF
R/W
Diameter
– diameter of the sensor.
Unit No.
– the serial number of unit.
Flow Qn
–expected flow Qn. It is set automatically when you write diameter.
Calibration Point 1
– calibration flow 1
Calibration Point 2
– calibration flow 2
Calibration Point 3
– calibration flow 3
Calibration Data 1
– calibration data 1
Calibration Data 2
– calibration data 2
Calibration Data 3
– calibration data 3
Note: CP1 < CP3 < CP2 and CD1 < CD3 < CD2.
The calibration point 3 and the calibration data 3 could be set to zero. CP1 < CP2 and CD1 < CD3.
Zero Flow Set
–
after activation this function, next 125 samples are compute to average value for zero flow
constant.
Zero Flow Constant
– Set manually value for zero flow constant.
Zero Flow Erase
– erase zero flow constant to 0.
Excitation Frequency
– choose the excitation frequency. For DN>450 the value must be 3,125Hz
Excitation
– write one for turn OFF the excitation.
CP1
CP2
CD2
CD1
Flow
ADC data
CP3
CD3
CD1 = Calibration data 1
CD2 = Calibration data 2
CD3 = Calibration data 3
CP1 = Calibration point 1
CP2 = Calibration point 2
CP3 = Calibration point 3
ADC data = data from AD
converter