MAGS1 User Guide
15
V1.5 22-1-2016
4.12. Real-time measurement
Modbus
register
Modbus
address
No. of
bytes
Data type
No. of
decimal
Min Value
Max Value
Description
Read/
Write
100
99
4
Longint
3
0
2^32
Actual Flow
R
102
101
4
Bool
0
0
1
Flow Sign
R
104
103
4
Longint
0
0
999 999 999 Total DIG
R
106
105
4
Longint
3
0
999
Total DEC
R
108
107
4
Longint
0
0
999 999 999 Total + DIG
R
110
109
4
Longint
3
0
999
Total + DEC
R
112
111
4
Longint
0
0
999 999 999 Total
– DIG
R
114
113
4
Longint
3
0
999
Total
– DEC
R
116
115
4
Longint
0
0
999 999 999 Aux + DIG
R
118
117
4
Longint
3
0
999
Aux + DEC
R
120
119
4
Longint
0
0
2^16
Error Code
R
122
121
4
Longint
0
- 8 388 608 8 388 607
Data from AD
converter
R
124
123
4
Longint
0
- 8 388 608 8 388 607
Average data from
AD converter
R
126
125
4
Longint
0
- 8 388 608 8 388 607
Empty pipe data
from AD converter
R
128
127
4
Longint
1
- 1500
2000
Temperature °C
R
Actual Flow
Unit: m3/h - it is not possible to change it.
Real value = Actual value / 1000.
Flow Sign
Sign of the read flow.
0
– positive flow
1
– negative flow
Total (Total +, Total -, Aux +)
Unit: m
3
– it is not possible to change it.
The final number is given by the sum of the whole and the decimal.
Example: Resulting Total measurement = (TOTAL DIG) + (TOTAL DEC*10^-3).
Error Code
Convert read value to binary code. For more information see chapter 10.
Data from AD converter
Raw data from AD converter. This data are averaging in average data from AD converter register.
Average data from AD converter
Average raw data from AD converter. This data are used for flow calculating according to calibration curve.
Empty pipe data from AD converter
Raw data from AD converter. This data are used for detection of empty pipe alarm. Threshold for detection
is possible to setup in Air constant register.
Temperature
Real value = Actual value divided by 10.
Unit: °C – it is not possible to change it.
If value of any volume counter is higher than 999 999 999 m3, then this volume will be reset
to 0.