35
Care and Maintenance
00
1.
14
15
5.3
3
r
ev
. 8
Testing the Ceiling Lift
Verifying the Soft Start and Soft Stop Features
Without Load
Press the
DOWN
button on the hand control. Observe as the vertical motor unravels the strap. The motor
should not reach its top speed instantly. Top speed should be achieved only after approximately 1 second
of time has elapsed.
With Load
1) Attach the WLT trolley to the ceiling lift. (Refer to Testing the Track (SWL Procedure) on page 25.)
2) Press the
UP
button on the hand control. Observe as the vertical motor winds up the strap. The motor
should not reach its top speed instantly. Top speed should be achieved only after approximately 1
second of time has elapsed.
If the soft start and stop features do not behave as described, please refer to the “Circuit Board
Replacement” procedure on page 9.
Verifying the Emergency Stop Feature
1) Attach the WLT trolley to the ceiling lift.
2) Raise the WLT trolley up to no more than 30 cm (1 ft) with the
UP
button on the hand control.
3) While keeping the
UP
button pressed, pull on the red emergency stop cord. The ceiling lift should shut
down and the raising action should cease.
If the emergency stop feature does not function as described, please refer to the “Circuit Board
Replacement” procedure on page 9.
Verifying the Emergency Lowering Device
1) Attach the WLT trolley to the ceiling lift.
2) Raise the WLT trolley up to no more than 30 cm (1 ft) with the
UP
button on the hand control.
3) Pull the red emergency cord to turn off power.
4) Open the small side door to access the lowering mechanism and remove the 8 mm hex key located on
the top of the ceiling lift.
5) Insert the hex key deep into the socket and turn the hex key counter-clockwise to slowly lower the WLT
trolley.
6) After a few turns, confirm that the WLT trolley is being lowered.
Verifying the Lifting Capacity of the Ceiling Lift Without Load
Raise the SWL trolley roughly 30 cm (1 ft) off the floor and wait 5 seconds.
• If you hear the current limiter signal, then the current limiter needs adjusting. Refer to the
programming manual (#001-14154-33) to adjust the maximum lifting capacity.
• If you hear the low battery signal, then ensure that the batteries are fully charged and repeat the
test to determine if the batteries need replacing.
CAUTION: Do not use a power drill to perform this test as the initial angular velocity of the drill
may damage the internal components of the ceiling lift’s transmission.