1X-X3E Series Operation Manual
27
Table 6: Additional output device test options
Output device
LED used
Test functionality
Actuator
Released yellow
The actuator output will be 3 seconds on, 5
seconds off, for the duration of the test.
A steady Released LED indicates that the
output is activated.
Extinguishing release
optical warning panel
or sign
Optical Panel On
yellow
The optical panel output will be 3 seconds on, 5
seconds off, for the duration of the test.
A steady Optical Panel On LED indicates that
the output is activated.
WARNING:
Risk of death or serious injury. Disconnect the extinguishing agent
actuator from the control panel
before
you issue the primary actuator output test
command. When you confirm the test command, the primary actuator output is
activated immediately.
Set the manual-only mode of operation
If the control panel is not configured to use an external input to switch to manual-
only mode, press the Manual Mode button on the control panel. Manual-only
mode is indicated by a steady Manual Mode LED. In this mode, the extinguishing
event can only be generated by activation of the MCP Start point. The fire
detection zones in the extinguishing area cannot generate the extinguishing
event.
Pressing the Manual Mode button again switches the control panel back to
automatic-manual mode. The Manual Mode LED turns off. In automatic-manual
mode, the detection zones in the extinguishing area and the MCP Start point can
generate the extinguishing event.
In addition, the control panel can be set to manual-only or manual-automatic
mode using the key switch, if your installer has configured this option.