1X-X3E Series Operation Manual
BS 7273 user interface
For control panels configured for BS 7273, the labels for some interface buttons
change. See Table 2 below.
Table 2: Configured changes to interface buttons and LEDs
Item
BS 7273 user interface
22
Auto/Manual mode and Only Manual mode button and LEDs
27
Extinguishing disabled switch LEDs
Operator controls and indicators
The following table gives an overview of the control panel operator controls and
indicators. Item numbers refer to Figure 1 on page 3.
Operational features described here may not be available to all users. Further
information on control panel operation and user restrictions can be found in
“Control panel operation” on page 18.
Table 3: Operator controls and LED indicators
Item
Control/LED
LED colour Description
1
Zone buttons and
LEDs (Z1, Z2, Z3)
Red/Yellow
Disables or tests a zone (when pressed with the
General Disable or General Test button).
A red LED indicates a fire alarm in the
corresponding zone.
A flashing red LED indicates that the fire alarm
was activated by a detector. A steady red LED
indicates that the fire alarm was activated by a
manual call point.
A flashing yellow LED indicates a wiring fault in
the corresponding zone. A steady yellow LED
indicates a disablement or a test.
2
Supply LED
Green
Indicates that the system is powered up.
3
General Fault LED
Yellow
Indicates a fault. The corresponding zone, device,
or function fault LED also activates.
4
General Fire Alarm
LEDs
Red
Indicates a fire alarm.
Flashing red LEDs indicate that the fire alarm was
activated by a detector.
Steady red LEDs indicate that the fire alarm was
activated by a fire manual call point.
For alarms from fire detection zones, the
corresponding zone alarm LED indicates the
source or location of the fire alarm.