9
Item
Control/LED
LED colour Description
22
Manual Mode button
and LED
Yellow
Used to change from manual-only mode to
manual-automatic mode and vice versa, if
configured.
A steady yellow LED indicates that the control
panel is in manual only mode: the automatic fire
detection zones cannot generate the
extinguishing event.
Your system installer may have disabled this
feature by configuring an external device that is
connected to a control panel input.
22
Auto/Manual mode
(BS 7273)
Yellow
A steady yellow LED indicates that the control
panel is in manual-automatic mode.
22
Only manual mode
(BS 7273)
Green
A steady green LED indicates that the control
panel is in manual-only mode.
23
System Fault LED
Yellow
Indicates a control panel processor failure.
24
Out of Service LED
Yellow
Indicates that control panel power supply
conditions have put fire detection zones and
inputs out of service.
Other system functions remain operational.
A steady yellow LED indicates that there is no
mains power and the battery power is insufficient.
A flashing yellow LED indicates that the mains
power is insufficient and there is no battery
power.
25
Earth Fault LED
Yellow
Indicates an earth isolation fault.
26
Supply Fault LED
Yellow
Indicates a fault in the power supply.
A flashing LED indicates a battery or battery fuse
fault. A steady LED indicates a mains or mains
fuse fault.
27
MCP Abort LEDs
Yellow
Indicates the abort manual call point status.
A steady upper yellow LED indicates that an abort
extinguishing manual call point has been
activated (the extinguishing process is cancelled).
A flashing lower yellow LED indicates an open or
short circuit wiring fault. A steady lower yellow
LED indicates a disablement or test.
An MCP Abort fault prevents entering activation
(because of life safety issues) and activating the
actuator (to ensure property protection).
27
Disable
extinguishing switch
(BS 7273)
Yellow
A steady upper yellow LED indicates that the
extinguishing switch is disabled.
A flashing lower yellow LED indicates an open or
short circuit wiring fault. A steady lower yellow
LED indicates a disablement or test.