10
1X-X3E Series Operation Manual
Item
Control/LED
LED colour Description
28
MCP Hold LEDs
Yellow
Indicates the hold manual call point status.
A steady upper yellow LED indicates that a hold
extinguishing manual call point is active, and the
extinguishing process is paused.
A flashing lower yellow LED indicates an open or
short circuit wiring fault, or that the extinguishing
hold activation is in a standby mode. A steady
lower yellow LED indicates a disablement or test.
An MCP Hold fault prevents entering activation
(because of life safety issues) and activating the
actuator (to ensure property protection).
29
MCP Start LEDs
Red/Yellow
Indicates the start manual call point status.
A steady red MCP Start LED indicates that a start
extinguishing manual call point has been
activated to create a manual extinguishing event.
A flashing yellow LED indicates an open or short
circuit wiring fault. A steady yellow LED indicates
a disablement or test.
30
Fire Routing Delay
button and LED
Yellow
Enables or disables a previously configured fire
routing delay. Fire routing is optional.
A steady LED indicates that a fire routing delay is
configured and enabled. A flashing LED indicates
that a fire routing delay countdown is in progress
(fire routing activates when the configured delay
elapses).
Consult your system installer to determine
whether the Fire routing option is configured.
31
Fire Routing On
button and LEDs
Red/Yellow
Overrides the configured delay (when this is
running) and activates fire routing. Disables or
tests fire routing (when pressed with the General
Disable or General Test button).
A flashing red LED indicates that fire routing is
activated.
A flashing yellow LED indicates a wiring fault. A
steady yellow LED indicates a disablement or a
test.
Consult your system installer to determine
whether the Fire routing option is configured.