1X-E4 Series Operation Manual
19
Disabling sounders or enabling sounders
To disable evacuation sounders, press the General Disable button, and then
press the Evacuation Area button.
Disabled evacuation sounders are indicated as follows
• General Disable LED: On steady.
• Evacuation Area LED: On steady yellow.
To enable the sounders, press the General Disable button, and then press the
Evacuation Area button again.
Note:
Disabled evacuation sounders do not operate or indicate faults.
Testing fire routing
Note:
Always notify the
fire brigade of any planned fire routing tests.
To test fire routing, press the General Test button, and then press the Fire
Routing Start button.
The test is indicated as follows:
• General Test LED: On steady.
• Fire Routing Start LEDs: Flashing red (3 seconds on, 5 seconds off) and
steady yellow.
• Fire routing outputs: Test signal (3 seconds on, 5 seconds off)
To end the test, press the General Test button, and then press the Fire Routing
Start button again.
If there is a fire alarm the fire panel will exit the test and respond to the alarm as
configured.
Disabling or enabling fire routing
To disable fire routing, press the General Disable button, and then press the Fire
Routing Start button.
Disabled fire routing is indicated as follows:
• General Disable LED: On steady.
• Fire Routing Start LED: On steady yellow.
To enable fire routing, press the General Disable button, and then press the Fire
Routing Start button again.
Note:
Disabled fire routing does not operate or indicate a fault if there is a fire
alarm.