1X-E4 Series Operation Manual
9
Tests
A zone test is indicated as follows:
• General Test LED: On steady.
• Corresponding Zone LED: On steady yellow.
• Control panel buzzer: Off.
An evacuation area test is indicated as follows:
• General Test LED: On steady.
• Evacuation Area: On steady yellow.
• Control panel buzzer: Off.
A fire routing test is indicated as follows:
• General Test LED: On steady.
• Fire Routing Start LED: On steady yellow.
• Control panel buzzer: Off.
Out of service
The control panel is out of service when there is insufficient or no mains or
battery power. Zone and input detection does not operate, but the rest of the
system is operational. In this state, the control panel may receive network events
which activate its outputs.
Out of service is indicated as follows:
• Out of Service LED: On steady.
• Supply Fault LED: Flashing if there is no mains power and the battery voltage
is insufficient. On steady if the mains power is insufficient and no battery
power is detected.
• Control panel buzzer: Sounding intermittent.
The out of service state latches. When power is re-established, the panel must
be reset to remove this fault.
Note:
When the control panel indicates
out of service,
your fire alarm and
evacuation system is partly inactive and your site is not properly protected.
Contact your installation or maintenance contractor immediately to investigate
the problem.