1X-E4 Series Operation Manual
7
Fire alarm
Fire alarm status is indicated as follows:
• General Fire Alarm LEDs: Flashing if the alarm was activated by a detector.
Steady if the alarm was activated by a manual call point.
• Zone LED: Flashing red if the alarm was activated by a detector. Steady red if
the alarm was activated by a manual call point. Shows which zones are in
alarm.
• Evacuation Area LED: On steady to indicate that sounders are active in those
areas (sounding).
• All Sounders Start LED is steady (if all evacuation areas are active).
• Fire Routing Delay LED: Flashing slow when a fire routing delay is active
(counting). Flashing fast when an extended fire routing delay is active
(counting).
• Fire Routing Start LED: Flashing when fire routing is activated. On steady
when the fire routing signal has been acknowledged by the remote monitoring
equipment.
• Control panel buzzer: Sounding continuous.
Alarms activated by a manual call point always take priority over alarms activated
by a detector. If an alarm is activated by both devices, the Fire Alarm LEDs and
Zone alarm (red) LEDs are on steady.
Evacuation
In evacuation status, the panel activates the sounders without detection of a
zone alarm. The status is indicated as described below.
• Evacuation Area LED: On steady to indicate that sounders are active in those
areas (sounding)
• All Sounders Start LED: On steady (if all evacuation areas are active)
• Control panel buzzer: Sounding continuous
Fault
Fault status is indicated as follows:
General fault indication:
• General Fault LED: Flashing.
• Corresponding zone, evacuation area, function, or device fault LED: Flashing
yellow.
• Control panel buzzer: Sounding intermittent.
Mains power fault and mains fuse fault indication:
• General Fault LED: Flashing.
• Supply Fault LED: On steady.