29
Gas Adjustments
2
3
4
C
E
F
D
5. To set the minimum power, disconnect a supply terminal “F1”
from the modureg and adjust scre w
“F” (ensure that the
10mm nut is held in position). Turn the scre w clockwise to
increase the pressure and anti-cloc kwise to decrease the
pressure (displayed on the pressure gauge) corresponding to
the minimum power (see
TABLE A page 28).
6. When you have completed the above operations, turn off the
hot water tap, reconnect the supply ter minal to the modureg
on the gas v alve, reconnect the compensation pipe and
replace the cap on the screw of the modureg.
Setting the maximum heating circuit power
7. To set the maxim um heating circuit po wer, push the On/Off
button to the “ON” position -green light- and push the Heating
button and set the time clock and any external controls to the
“ON” position -green light. Turn the knob of the heating ther-
mostat clockwise to maximum.
8. Remove the inspection panel of the P .C.B. and fit a small
cross-head screwdriver in to the right hand potentiometer (see
below). Turn clockwise to increase the pressure or counter-
clockwise to reduce the pressure . Adjust the setting to the
required heating pressure v alue (displayed on the pressure
gauge), as indicated in the char ts shown on pages 28.
9. Turn off the boiler b y placing the main s witch to the "OFF"
position.
Setting the pressure for soft-light ignition.
Disconnect the detection electrode connection close to the
P.C.B. (F
IG
. 6.13).
Start the boiler and during the ignition sequence adjust the left
hand potentiometer until the gas pressure reads the required
gas pressure
(see the table on page 28).
Once the gas pressure is set turn off the boiler and re-connect
the detection electrode to the P.C.B.
NB.: It may be necessar y to reset the flame f ailure reset a
number of times during this operation.
10. Remove the pipe from the test point and tighten the screw “C”
to the pressure test point in order to seal off the gas .
11. Carefully check the pressure test points f or gas leaks (valve
inlet and outlet).
IMPORTANT!
Whenever you disassemble and reassemb le the gas connec-
tions, always check for leaks using a leak detection fluid.
Max Heating
Adjustment
Soft - Light
Adjustment
Summary of Contents for INTESA TP23
Page 44: ...44 Fault Finding...
Page 45: ...45 Fault Finding...
Page 46: ...46 Fault Finding 0 55mbar 23kW 0 90mbar 30kW 0 55mbar 23kW 0 90mbar 30kW...
Page 47: ...47 Fault Finding...
Page 50: ...50...
Page 51: ...51...