13
Installation
25 mm
25 mm
25 mm
F
IG
6.9
F
IG
6.10
F
IG
6.11
WARNING
IT WILL BE NECESSARY
TO CONSULT
T
ABLE
6.1
ON PAGE
18
TO
DETERMINE WHETHER
THE FLUE RESTRICTOR
IS REQUIRED
.
SHOULD
IT NOT BE NEEDED
,
THE RESTRICTOR WILL
NEED TO BE REMOVED
FROM THE FLUE GAS
COLLAR
(F
IG
. 6.11).
face of the flue elbo w
(X - F
IG
6.8), add 22 mm to this measure-
ment, you now have the total length of flue required (including the
terminal), this figure m ust now be subtracted from 860mm, y ou
now have the total amount to be cut from the plain end of the flue.
Cut the flue to the required length ensur
ing that the distance
between the inner and the outer flue is maintained
(F
IG
6.10).
e.g. X = 508mm + 22mm = 530mm
860 - 530 = 330mm (Length to be cut from the plain end
of the flue).
Once cut to the required length, ensure that the flue is free from
burrs and reassemble the flue. If fitting the flue from inside of the
building attach the g rey outer wall seal to the flue ter minal and
push through the flue through the hole , once the w all seal has
passed through the hole, pull the flue bac k until the seal is flush
with the wall. Alternatively, the flue can be installed from outside
of the building, the grey outer seal being fitted last.
Fitting the Telescopic Flue Kit (Horizontal)
C
ONTENTS
:
1
X
S
ILICONE
O-R
ING
(60mm)
1
X
E
LBOW
(90
O
)
2
X
W
ALL
S
EALS
(I
NTERNAL
& E
XTERNAL
)
1
X
A
LUMINIUM
F
LUE
P
IPE INCLUDING
T
ERMINAL
(T
ELESCOPIC
- 60/100)
2
X
F
LUE
C
LAMPS
8
X
S
CREWS
2
X
S
EALS
The telscopic flue is suitab le for use with an e xact minimum
X
dimension of 270mm and an e xact maximum X dimension
470mm.
IMPORTANT!!
Do not extend the telescopic flue to an X dimension of more
than 470mm. If longer lengths are required use e xtension
pieces as necessary. Under no circumstances must the flue
be cut.
The wall must then be made good around the flue (ensuring a fall
of 1
o
is maintained away from the boiler to the flue ter minal).
Once made good, place the inner (white) w all seal over the flue
and push up to the wall, secure the flue to the elbow by using the
clamp supplied.
For each additional 90
o
elbow 1 metre must be removed from the
total flue length (maximum 4 metres including the 1st elbow). For
each additional 45
o
elbow 0.5 metre must be subtracted from the
total flue length (
F
IG
6.13).
Fitting the Coaxial Flue (Vertical)
(For Twin Pipe Instructions see page 14)
C
ONTENTS
:
1
X
S
ILICONE
O-R
ING
(60mm)
1
X
E
LBOW
(90
O
)
2
X
W
ALL
S
EALS
(I
NTERNAL
& E
XTERNAL
)
1
X
A
LUMINIUM
F
LUE
P
IPE INCLUDING
T
ERMINAL
(T
ELESCOPIC
- 60/100)
2
X
F
LUE
C
LAMPS
8
X
S
CREWS
2
X
S
EALS
The vertical flue kit is supplied with a specially designed weather
proof terminal fitted, it can be used either with a flat roof or a
pitched roof. (see
F
IGS
6.12, 6.13).
F
IG
6.12