49
1. Carry out steps 18.2.1 and 18.4.1;
2. Disconnect the wire connectors “L1” and the earth wire
“L2”
(see Fig. 18.35);
3. Remove the screw “M” fixing the fan on the flue outlet,
(see Fig. 18.35);
4. Slide the fan to disengage from flue outlet and lift clear
(see Fig. 18.35, 18.36, 18.37);
5. Disconnect the pressure pipes noting positions (see Fig. 18.38);
6. Reassemble in reverse order ensuring that the wiring is
reconnected correctly and the screw tightened.
18.4.8 Removing the fan
1. Carry out steps 18.2.1 and 18.4.1;
2. Disconnect the wire connectors “K1” (see Fig. 18.33);
3. Disconnect the pressure pipes “K2” noting positions
(see Fig. 18.33 );
4. Rotate the the pressure switch clockwise to disengage
it (see Fig. 18.34);
5 Reassemble in reverse order ensuring that the wiring is
reconnected.
18.4.7 Removing the air pressure switch
Fig. 18.33
Fig. 18.34
Fig. 18.35
Fig. 18.38
Fig. 18.36
Fig. 18.37
K1
K2
L1
L2
M