NB:  In  case  of  prolonged  non-use  of  the  rat  water,  the  siphon  

MUST  BE  FILLED  BEFORE  A  NEW  START.

LACK  OF  WATER  IN  THE  SIPHON  IS  DANGEROUS  AND  CAN  

CAUSE  SMOKE  TO  COME  OUT  INTO  THE  ATMOSPHERE.

MAINTENANCE

/  

25  

7.  Checking  the  operation  of  the  safety  systems  on  the  side  of

Cleaning  the  primary  exchanger  

Connect  to  the  primary  heat  exchanger  by  removing  the  burner  -  see  

Fig.  The  heat  exchanger  is  cleaned  with  a  non-metallic  brush  and  a  
vacuum  cleaner.

-  switch  off  (switch  off)  the  boiler  and  set  the  external  bipolar  switch  to  

the  OFF  position  and  close  the  gas  valve;

5.  Cleaning  the  main  heat  exchanger.

Seal  the  openings  used  to  read  the  gas  pressure  or  gas  settings.

It  is  recommended  that  periodic  flue  gas  (combustion)  analysis  be  
performed  to  monitor  the  efficiency  and  emissions  of  pollutants  in  
accordance  with  applicable  regulations.

drains  into  a  water  tank;

10.  Remove  the  oxide  from  the  ionization  electrode  with  a  piece  of  

rough  cloth  (DO  NOT  use  sandpaper!)

Also  clean  the  flue  (located  in  

front  of  the  heat  exchanger)  
before  mounting.

It  is  advisable  to  carry  out  the  following  checks  (checks)  on  the  

appliance  at  least  once  a  year:

-  safety  without  gas  or  flame  (ionization).

DO  NOT  use  acidic  liquids  or  

detergent.

Function  test  After  
carrying  out  maintenance  and  inspection  work,  refill  the  heating  circuit  
at  a  pressure  of  approx.  1.0  bar  and  ventilate  the  system.  Refill  the  
domestic  water  system  as  well.

3.  Eye-check  of  the  overall  condition  of  the  appliance.

Whenever  there  is  a  danger  of  frost,  the  sanitary  installation  must  be  
emptied  as  follows:

Washing  can  be  done  with  water  and  detergent.

-  evacuate  from  the  lowest  points  of  the  installation  (where  they  are

gas:

When  removing  the  siphon,  use  
a  suitable  container  to  collect  
condensate  that  may  leak  from  
the  boiler.

-  loosen  (open)  the  automatic  exhaust  valve;

6.  Checking  the  operation  of  the  heating  safety  systems:

-  Check  the  insulation  (tightness)  and  proper  operation  of  the  flue  gas /  

combustion  supply  system  required  for  combustion  (combu  rent).

DO  NOT  MIX  DIFFERENT  TYPES  OF  ANTIFREEZE.

CAREFUL

Before  starting  maintenance:

Refit  the  condenser  tank.

Maintenance  (inspection,  overhaul)  is  essential  for  the  safety,  proper  

operation  and  life  of  the  boiler.

1.  Checking  the  insulation  gaskets  (support)  on  the  water  side  with  the  

possible  replacement  of  the  gaskets  and  restoring  the  tightness.

8.  Control  of  domestic  water  production  efficiency  (bit  and  temperature  

verification).

Careful!

Make  sure  the  nozzle  is  compatible  with  the  supply  gas.

-  Switch  on  the  appliance.

4.  As  a  result  of  the  check  in  point  3,  any  disassembly  and

-  Turn  off  the  water  tap,

-  electrically  disconnect  the  boiler  and  set  the  external  bipolar  switch  to  

the  OFF  position  -  close  the  gas  tap  and  the  water  taps  of  the  

heating  and  plumbing  installations;

provided).

The  presence  of  oxide  on  the  heat  exchanger  does  not  affect  the  
performance  of  the  boiler.  If  you  feel  the  need  to  clean  the  heat  

exchanger,  follow  the  steps  below.

Soda  cleaning

Installation  emptying  operations

The  manufacturer  is  not  responsible  for  any  damage  caused  to  the  

water  or  system  and  caused  by  the  use  of  unsuitable  antifreeze  or  

additives.

Empty  components  that  may  contain  hot  water  by  activating  any  drain  
valves  before  handling  them.

-  If  necessary,  ventilate  the  heating  system  again.

If  it  is  intended  to  keep  the  system  switched  off  in  areas  where  the  

ambient  temperature  may  drop  below  0  °  C  during  the  winter,  it  is  
advisable  to  add  antifreeze  liquid  to  the  water  in  the  heating  system  to  
avoid  repeated  drainage;  If  you  use  such  a  liquid,  please  contact  the  
ARISTON  Service  Center  for  any  further  information  on  the  most  

suitable  products  to  use.

-  open  all  hot  and  cold  water  taps,

-  open  the  drain  valve  of  the  installation  by  squeezing  the  water  that

-  temperature  limit  safety.

If  you  smell  or  see  smoke  coming  out  of  the  appliance  or  smell  strong  

gas,  turn  off  the  power  supply,  turn  off  the  gas  tap,  open  the  windows,  
and  inform  your  technician.

cleaning  the  combustion  chamber

Carry  out  the  unclogging  (unclogging)  of  the  limescale  of  the  components  
in  accordance  with  the  specifications  in  the  safety  data  sheet  of  the  

product  used,  ventilating  the  environment,  using  protective  equipment,  
avoiding  mixing  different  products,  protecting  the  appliance  and  the  
surrounding  objects.

At  the  end,  the  initial  settings  are  played  back  (resumed).

replacement  of  gaskets  and  restoration  of  tightness.

It  is  carried  out  in  accordance  with  the  provisions  of  the  rules  in  force.

2.  Checking  the  insulation  gaskets  on  the  gas  side  if  necessary

9.  General  control  of  the  operation  of  the  appliance.

It  is  mandatory  to  replace  the  

gasket  (see  figure)  each  time  

the  burner  is  removed.

The  heating  system  must  be  emptied  as  follows:

-  Check  the  settings  and  proper  operation  of  all  control,  adjustment  and  

control  devices.

Periodically  check  the  pH  of  the  water-antifreeze  mixture  (between  7  

and  8)  in  the  boiler  circuit  and  replace  the  mixture  when  the  measured  

value  is  less  than  the  limit  prescribed  by  the  manufacturer.

-  empty  from  the  bottom  points  (where  provided).

Draining  the  sanitary  installation

The  siphon  is  reached  by  avoiding  the  condensate  at  the  bottom.

General  Notes

Machine Translated by Google

Summary of Contents for 3300761

Page 1: ...NSING WALL THERMAL POWER PLANT HS PREMIUM 420000255500 3300761 3300765 HOT WATER I HEATING I RENEWABLE I AIR CONDITIONING TECHNICAL INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE Machine Translated by Google ...

Page 2: ...amp plate 26 Installation 9 Recommendations for the first installation 9 Gas connection 9 Connection to the water network hydraulic 10 Hydraulic connections 10 Graphical representation of the residual flow recirculation pump 10 Overpressure Device 10 Cleaning the heating system 10 Underfloor heating installations 10 Condensate drain 11 Hydraulic diagram 11 Connection of flue and exhaust pipes 12 T...

Page 3: ...s AFTER THE FIRST START OF THE POWER PLANT THE TECHNICIAN MUST INFORM THE END USER ABOUT This appliance is intended for the production of domestic hot water for domestic use and heating for heating Any repairs carried out using only original spare parts must be carried out only by qualified technicians Failure to observe the above instructions could compromise the safety of the device and the manu...

Page 4: ...o which the appliance is to be connected comply with the applicable regulations Damage to the appliance due to improper operating conditions Make sure that the castle stairs are well supported stable sturdy that the steps are complete and non slip that they have railings along the ramp and parapets on the platform Noise during operation Damage to the device or objects around it due to the design o...

Page 5: ...they are working properly Damage to the appliance or objects around it due to corrosion by substances Damage to the appliance or objects around it due to blows cuts crushes Handle the appliance with adequate protection with the utmost care and caution Explosions fires or poisoning due to gas leaks or improper exhaust fumes Equip yourself with the appropriate personal protective equipment during wo...

Page 6: ...heating circuit Report error codes Active heating request Request to press the Reset key central locked Figures for indications 3 Display The legend 4 keys to adjust the temperature in the heating circuit 1 ON OFF key and select operating mode 5 RESET key summer Winter Display 2 keys to regulate the temperature in the sanitary circuit Control panel 6 4 2 1 5 3 PRODUCT DESCRIPTION Machine Translate...

Page 7: ...14 Minimum load pressure switch 15 Heating return probe 16 Main plate 17 Burner 18 Valve gas 19 Fan 20 Outlets for flue gas analysis smoke A Installation Tour Place the boiler in accordance with the technical rules using a bubble level The legend Minimum distances for installation In order to allow easy maintenance overhaul of the boiler it is necessary to observe the minimum distances indicated i...

Page 8: ...353 compact Installation template 320 8 420020122200 03 2015 30 136 60 PRODUCT DESCRIPTION Machine Translated by Google ...

Page 9: ...of the boiler Before connecting the boiler it is necessary to In addition it is important to check that the gas pressure methane or LPG to be used to power the boiler if insufficient could reduce the power of the burner with unpleasant consequences on the user s comfort The boiler is used to heat the heating agent to a temperature lower than the boiling temperature carry out a thorough cleaning of...

Page 10: ...imals and damage to property for which the manufacturer is not responsible long term proper operation of the plant Water treatment H Drain valve Rinse the entire heating system For the dimensioning of the pipes and radiators of the heating installation the residual level value is evaluated according to the required flow capacity according to the values presented on the recirculation pump graph If ...

Page 11: ...pressure switch 5 Secondary plate heat exchanger 14 Recirculation pump with vent valve 6 By pass automat 12 INSTALLATION CAREFUL EMISSIONS OF SMOKE EMPTYED INTO AMBIENT AIR THE ABSENCE OF WATER IN THE SIPHON CAUSES 11 I 8 9 3 10 16 5 11 6 15 7 19 1 18 17 4 14 13 20 2 it must not be tight at the time of connection Observe the installation regulations in force in the country where the installation i...

Page 12: ...s made of flammable materials The connection connection of the flue gas pipes is made with a male female connection plug and a sealing gasket Condensation resistant products must be used when connecting the boiler to the chimney For connection lengths and changes see the exhaust type table The connections must be placed against the direction of condensate leakage The boiler is suitable for operati...

Page 13: ...Flue gas exhaust and air intake through individual or collective chimney integrated in the building S1 air intake S2 exhaust gas C83 Flue gas exhaust through individual or collective chimney integrated in the building S1 S2 C43 HS PREMIUM B33 ø 60 100 ø 80 30 EU C33 Diameter C13 10 42 25 25 25 B23 Exhaust flue gas C13 10 42 C83 C53 Exhaust gas exhaust and air intake through the external wall in th...

Page 14: ... the safety of the device The boiler is not protected against the effects of lightning If network fuses need to be replaced use fast 2A fuses BUS camera sensor connection device modulating SE External Probe TA1 Room thermostat 1 H05V2V2 F connector peripheral equipment Connecting accessories and peripheral equipment Insert the thermostat wires into the opening next to it Replace the control panel ...

Page 15: ...ailure of the system to be grounded or for power outages Mr ÿmaro No black For a better safety qualified personnel are inspected by the electrical installation Room thermostat 1 and Rs red Bi alb Gr gray heated floor thermostat Bl blue 1 3 4 5 6 2 7 Games Press to switch tour at the probe Switching valve 3 horsepower motorized Ventilator firer Recirculation pump Recirculation pump Sanitary flow me...

Page 16: ...e which will last approximately 7 minutes the flue pipe must be e Eliminate any gas leaks the electrical connection is made correctly make sure that all vents windows in the room are open type B installation operation heating or domestic hot water a the mode of operation set with the symbols and b the numbers show Ignition procedure yellow is connected to a good earthing system must be refilled in...

Page 17: ...1 minute for the boiler to stabilize before performing the combustion analysis Operation 3 Adjust the CO2 level to the maximum gas flow The order of operations must be followed in this procedure Measure the value of the CO2 level and compare it with the values in the table below If the value of the measured CO2 level is different CAREFUL By activating the TEST function the water temperature at the...

Page 18: ...ntil the pressure is correct It is possible to adjust the maximum heating power between the maximum permissible appliance and the minimum At maximum power 100 will be displayed at minimum 00 will be displayed Maximum heating power setting parameter 231 ATTENTION If the CO2 value at minimum power has been changed it is necessary to resume the adjustment of the gas valve at maximum power To control ...

Page 19: ...Auto function is deactivated has the role of moving the curve in parallel For detailed information refer to the CHAFFOTEAUX Thermoregulation Manual Auto function The function allows the boiler to automatically adapt to the operating mode radiator temperature and to the external conditions in order to reach and keep the set ambient temperature constant 421 Activation Thermoregulation with sensors D...

Page 20: ...nomaly occurred is followed by the letter P ad and the code for that ad 2 Sanitary Circuit gear change in progress signals circulatory blockage or lack of water While the boiler is in safe stop you may want to try restarting it by turning the unit off and on again from the control panel Conditions for switching off the appliance 4 External Electronic Part They can be verified as two types of stops...

Page 21: ...imum power until the temperature reaches 33 C Ignition and Detection 1 P3 1 07 3 04 Too much RESET Primary circuit 6 12 Insufficient fan speed 5 02 Detection of flame with gas valve closed 3 06 Main board error Optional solar kit 1 10 Open circuit Short circuit heating probe 1 03 1 14 Open circuit Short circuit external heating probe 2 05 3 P9 Scheduled maintenance call for technical assistance 4 ...

Page 22: ...to 100 100 1 Timed Access to setting adjustment parameters diagnostics SAT RESERVED Only in case of change of gas or electronic board 231 Heating power adjustment max from 0 to 100 2 press the key to select the code Careful Parameters that can only be changed by specialized installers can be accessed only after entering the code 4 The first available parameter appears on the display to select the ...

Page 23: ...sible to move the heat curve in parallel Each step corresponds to an increase 2 indoor probe only 421 Select the basic thermoregulation type according to the connected peripherals 832 Heat return temperature C When using the outdoor probe the boiler calculates the most suitable flow temperature taking into account the outdoor temperature and the type of installation 0 anti limescale stop at 67 C 0...

Page 24: ...crew the two screws on the front panel b pull it forward and detach it from the top hooks c d Before carrying out any operation on the boiler disconnect it from the power supply by closing the external bipolar switch and the gas valve 1 remove the crankcase by removing it from the housing a 24 b c a d MAINTENANCE Machine Translated by Google ...

Page 25: ...Switch on the appliance 4 As a result of the check in point 3 any disassembly and Turn off the water tap electrically disconnect the boiler and set the external bipolar switch to the OFF position close the gas tap and the water taps of the heating and plumbing installations provided The presence of oxide on the heat exchanger does not affect the performance of the boiler If you feel the need to cl...

Page 26: ...n gas category Periodically check the water pressure in the installation inform him about filling the installation with water and ventilating the radiators Performs according to the norms the maintenance operations of the installation 1 Brand 8 Installation type 17 Boiler power calibration 3 Mode Serial No 10 Maximum sanitary pressure 19 Usable gas 12 Boiler type 21 Maximum heating temperature 14 ...

Page 27: ...ific value of domestic hot water max min Pci Qn C 8 Min max heating temperature low temperature range 61 29 0 6 0 B23 B23p B33 Minimum ambient operating temperature C Minimum hot water flow Pa 22 97 5 88 0 0 7 0 03 3 A 108 3 97 5 24 EU kW 5 36 60 Excess air 80 C 60 C 5 24 4 5 9 Yield at rated calorific value 60 80 C Hi Hs Max power min 50 C 30 C Pn 230 50 36 60 Air pressure available 30 2 6 4 Weig...

Page 28: ...IARY CONSUMPTION OF ELECTRICITY Acoustic power level inside LWA HS PREMIUM EU gives ARISTON THERMO S p A 28 gives not 6 9 85 0 034 37 Template AN ITALIA Energy efficiency related to water heating ÿwh 88 1 OTHER PARAMETERS not Viale A Merloni 45 60044 FABRIANO 28 4 84 0 013 64 kW Yes No kW 24 EU ErP HEATING Daily electricity consumption Qelec Pstby standby heat loss gives not HS PREMIUM Boiler type...

Page 29: ...ng the seasonal energy efficiency class of the dual function heating system package temperature controller and solar device shall be at the same height as the arrowhead on the corresponding energy efficiency class 5 Indication 3 the class of seasonal energy efficiency related to the heating of the premises of the installation for heating the premises already loaded 4 the classes of seasonal energy...

Page 30: ...m the product sheet of the solar device for the declared load profile M L XL and XXL of the dual function heating installation I the value of the seasonal energy efficiency related to the heating of the premises of the heating installation with preferential double function expressed in III value of the mathematical expression Qaux 2 5 220 Qref expressed in where Qaux is taken from the product shee...

Page 31: ...other factors such as heat loss in the distribution system and product sizing in relation to the size and characteristics of the building Energy efficiency of water heating of the dual function heating system 2 I G 1 I 0 2 x AND Solar contribution From the saddle of the solar device Energy efficiency of water heating of the package in average climatic conditions C Energy efficiency classes related...

Page 32: ...Polona Street 1st Floor 010505 1st District Bucharest ITALIAN DESIGN Phone 004021 2319521 Fax 004021 2319510 e mail service ro aristonthermo com www ariston com ro Ariston Thermo Romania srl 199 111 222 Machine Translated by Google ...

Reviews: