-  check  the  earthing  efficiency.

Proceed  as  follows:

Filling  the  installation  with  water

-  check  if  the  type  of  gas  supplied  corresponds  to  the  one  indicated  on  

the  stamp  plate  of  the  boiler;

-  open  doors  and  windows;

Proceed  as  follows:

-  open  the  tap  on  the  flow  circuit  (cold  water  supply);

-  avoid  sparks  and  open  flames;

In  order  to  guarantee  the  safety  and  proper  operation  of  the  plant,  

commissioning  must  be  carried  out  by  a  qualified  technician  who  is  

authorized  by  law  to  do  so.

-  remove  the  automatic  vent  valve  cover  from  the  pump

-  check  the  tightness  of  the  fuel  system  with  the  boiler  shut-off  valve  

closed  and  then  open,  and  the  gas  valve  closed  (deactivated)  for  
10  minutes  the  meter  (gas  sensor)  must  not  indicate  any  gas  
passage.

Power  supply

circulation;

-  Check  that  the  supply  voltage  and  frequency  match  yes

-  gradually  open  the  filling  valve  and  close  the  ventilation  valves  

on  the  radiators  as  soon  as  the  water  comes  out

-  close  the  boiler  filling  valve  when  the  pressure  indicated  on  the  

hydrometer  is  1  bar.

tele  inscribed  on  the  stamp  plate  of  the  power  plant;

Gas  supply

PUTTING  INTO  SERVICE

1  

16 /  

The  performance  of  certain  functions  is  also  indicated:

NB:  If  the  boiler  is  not  used  for  a  long  time,  the  siphon  
must  be  refilled  before  starting  the  boiler.  The  siphon  
acts  as  a  hydraulic  barrier,  and  it  is  dangerous  to  start  

the  boiler  without  water  in  the  siphon,  because  the  
flue  gases  can  be  released  into  the  room.

-  activate  the  deaeration  cycle  by  pressing  the  1  key  for  

10  seconds.  The  plant  will  begin  a  deaeration  cycle  of  
approximately  7  minutes.

1.  Make  sure  that:

Pressing  key  1  for  10  seconds  will  
start  the  boiler  cycle  which  will  last  
approximately  7  minutes.

-  the  flue  pipe  must  be  e

Eliminate  any  gas  leaks.

-  the  electrical  connection  is  made  correctly.

-  make  sure  that  all  vents /  windows  in  the  room  are  open  

(type  B  installation).

operation  (heating  or  domestic  hot  water).

a  -  the  mode  of  operation  set  with  the  symbols  and  b  -  the  

numbers  show:

Ignition  procedure

yellow  is  connected  to  a  good  earthing  system;

must  be  refilled.

-  in  the  sanitary  circuit  mode,  the  set  temperature  of  the  domestic  
horse  water

Preparation  for  commissioning

the  installation,  

on  the  pressure  gauge,  is  higher  

than  1  bar;  -  start  the  boiler  (by  

pressing  the  On /  Off  key)  and  

select  the  standby  mode,  there  

are  no  demands,  neither  from  
the  household  circuit  nor  from  
the  heating  circuit.

First  start

3.  Open  the  gas  valve  and  check  the  tightness  of  the  

connections,  including  those  of  the  boiler,  checking  that  

the  measuring  device  does  not  signal  any  gas  passage.

-  at  the  end  of  it,  check  that  there  is  no  more  air  in  the  

installation;  otherwise,  repeat  the  operation;

-  ventilate  the  radiators;

-  the  gas  valve  is  closed;

Ventilation  function

4.  Start  the  boiler  by  selecting  with  Key  1

2.  Check  that  the  siphon  contains  water.  If  not,  check  it

In  any  case,  make  sure  that  the  ground  wire  is  green /

Burner  ignites:  If  this  does  not  happen  on  the  first  try,  

repeat  the  operation  until  it  ignites.

adequate  and  without  any  obstacles

The  function  can  be  interrupted  by  

pressing  the  1  key  again .  If  

necessary,  you  can  activate  a  new  

cycle.  Check  that  the  boiler  is  also  in  Standby  mode  

(no  request  from  the  heating  or  sanitary  circuit).

Press  the  ON /  OFF  key  on  the  control  panel  to  turn  on  the  
boiler:

-  in  heating  mode,  flow  temperature

-  lift  the  automatic  overpressure  

valve  plug  with  a  screwdriver;

Deaeration  cycle  started

Post-circulation  heating

Post-circulation  domestic  hot  water

Machine Translated by Google

Summary of Contents for 3300761

Page 1: ...NSING WALL THERMAL POWER PLANT HS PREMIUM 420000255500 3300761 3300765 HOT WATER I HEATING I RENEWABLE I AIR CONDITIONING TECHNICAL INSTRUCTIONS FOR INSTALLATION AND MAINTENANCE Machine Translated by Google ...

Page 2: ...amp plate 26 Installation 9 Recommendations for the first installation 9 Gas connection 9 Connection to the water network hydraulic 10 Hydraulic connections 10 Graphical representation of the residual flow recirculation pump 10 Overpressure Device 10 Cleaning the heating system 10 Underfloor heating installations 10 Condensate drain 11 Hydraulic diagram 11 Connection of flue and exhaust pipes 12 T...

Page 3: ...s AFTER THE FIRST START OF THE POWER PLANT THE TECHNICIAN MUST INFORM THE END USER ABOUT This appliance is intended for the production of domestic hot water for domestic use and heating for heating Any repairs carried out using only original spare parts must be carried out only by qualified technicians Failure to observe the above instructions could compromise the safety of the device and the manu...

Page 4: ...o which the appliance is to be connected comply with the applicable regulations Damage to the appliance due to improper operating conditions Make sure that the castle stairs are well supported stable sturdy that the steps are complete and non slip that they have railings along the ramp and parapets on the platform Noise during operation Damage to the device or objects around it due to the design o...

Page 5: ...they are working properly Damage to the appliance or objects around it due to corrosion by substances Damage to the appliance or objects around it due to blows cuts crushes Handle the appliance with adequate protection with the utmost care and caution Explosions fires or poisoning due to gas leaks or improper exhaust fumes Equip yourself with the appropriate personal protective equipment during wo...

Page 6: ...heating circuit Report error codes Active heating request Request to press the Reset key central locked Figures for indications 3 Display The legend 4 keys to adjust the temperature in the heating circuit 1 ON OFF key and select operating mode 5 RESET key summer Winter Display 2 keys to regulate the temperature in the sanitary circuit Control panel 6 4 2 1 5 3 PRODUCT DESCRIPTION Machine Translate...

Page 7: ...14 Minimum load pressure switch 15 Heating return probe 16 Main plate 17 Burner 18 Valve gas 19 Fan 20 Outlets for flue gas analysis smoke A Installation Tour Place the boiler in accordance with the technical rules using a bubble level The legend Minimum distances for installation In order to allow easy maintenance overhaul of the boiler it is necessary to observe the minimum distances indicated i...

Page 8: ...353 compact Installation template 320 8 420020122200 03 2015 30 136 60 PRODUCT DESCRIPTION Machine Translated by Google ...

Page 9: ...of the boiler Before connecting the boiler it is necessary to In addition it is important to check that the gas pressure methane or LPG to be used to power the boiler if insufficient could reduce the power of the burner with unpleasant consequences on the user s comfort The boiler is used to heat the heating agent to a temperature lower than the boiling temperature carry out a thorough cleaning of...

Page 10: ...imals and damage to property for which the manufacturer is not responsible long term proper operation of the plant Water treatment H Drain valve Rinse the entire heating system For the dimensioning of the pipes and radiators of the heating installation the residual level value is evaluated according to the required flow capacity according to the values presented on the recirculation pump graph If ...

Page 11: ...pressure switch 5 Secondary plate heat exchanger 14 Recirculation pump with vent valve 6 By pass automat 12 INSTALLATION CAREFUL EMISSIONS OF SMOKE EMPTYED INTO AMBIENT AIR THE ABSENCE OF WATER IN THE SIPHON CAUSES 11 I 8 9 3 10 16 5 11 6 15 7 19 1 18 17 4 14 13 20 2 it must not be tight at the time of connection Observe the installation regulations in force in the country where the installation i...

Page 12: ...s made of flammable materials The connection connection of the flue gas pipes is made with a male female connection plug and a sealing gasket Condensation resistant products must be used when connecting the boiler to the chimney For connection lengths and changes see the exhaust type table The connections must be placed against the direction of condensate leakage The boiler is suitable for operati...

Page 13: ...Flue gas exhaust and air intake through individual or collective chimney integrated in the building S1 air intake S2 exhaust gas C83 Flue gas exhaust through individual or collective chimney integrated in the building S1 S2 C43 HS PREMIUM B33 ø 60 100 ø 80 30 EU C33 Diameter C13 10 42 25 25 25 B23 Exhaust flue gas C13 10 42 C83 C53 Exhaust gas exhaust and air intake through the external wall in th...

Page 14: ... the safety of the device The boiler is not protected against the effects of lightning If network fuses need to be replaced use fast 2A fuses BUS camera sensor connection device modulating SE External Probe TA1 Room thermostat 1 H05V2V2 F connector peripheral equipment Connecting accessories and peripheral equipment Insert the thermostat wires into the opening next to it Replace the control panel ...

Page 15: ...ailure of the system to be grounded or for power outages Mr ÿmaro No black For a better safety qualified personnel are inspected by the electrical installation Room thermostat 1 and Rs red Bi alb Gr gray heated floor thermostat Bl blue 1 3 4 5 6 2 7 Games Press to switch tour at the probe Switching valve 3 horsepower motorized Ventilator firer Recirculation pump Recirculation pump Sanitary flow me...

Page 16: ...e which will last approximately 7 minutes the flue pipe must be e Eliminate any gas leaks the electrical connection is made correctly make sure that all vents windows in the room are open type B installation operation heating or domestic hot water a the mode of operation set with the symbols and b the numbers show Ignition procedure yellow is connected to a good earthing system must be refilled in...

Page 17: ...1 minute for the boiler to stabilize before performing the combustion analysis Operation 3 Adjust the CO2 level to the maximum gas flow The order of operations must be followed in this procedure Measure the value of the CO2 level and compare it with the values in the table below If the value of the measured CO2 level is different CAREFUL By activating the TEST function the water temperature at the...

Page 18: ...ntil the pressure is correct It is possible to adjust the maximum heating power between the maximum permissible appliance and the minimum At maximum power 100 will be displayed at minimum 00 will be displayed Maximum heating power setting parameter 231 ATTENTION If the CO2 value at minimum power has been changed it is necessary to resume the adjustment of the gas valve at maximum power To control ...

Page 19: ...Auto function is deactivated has the role of moving the curve in parallel For detailed information refer to the CHAFFOTEAUX Thermoregulation Manual Auto function The function allows the boiler to automatically adapt to the operating mode radiator temperature and to the external conditions in order to reach and keep the set ambient temperature constant 421 Activation Thermoregulation with sensors D...

Page 20: ...nomaly occurred is followed by the letter P ad and the code for that ad 2 Sanitary Circuit gear change in progress signals circulatory blockage or lack of water While the boiler is in safe stop you may want to try restarting it by turning the unit off and on again from the control panel Conditions for switching off the appliance 4 External Electronic Part They can be verified as two types of stops...

Page 21: ...imum power until the temperature reaches 33 C Ignition and Detection 1 P3 1 07 3 04 Too much RESET Primary circuit 6 12 Insufficient fan speed 5 02 Detection of flame with gas valve closed 3 06 Main board error Optional solar kit 1 10 Open circuit Short circuit heating probe 1 03 1 14 Open circuit Short circuit external heating probe 2 05 3 P9 Scheduled maintenance call for technical assistance 4 ...

Page 22: ...to 100 100 1 Timed Access to setting adjustment parameters diagnostics SAT RESERVED Only in case of change of gas or electronic board 231 Heating power adjustment max from 0 to 100 2 press the key to select the code Careful Parameters that can only be changed by specialized installers can be accessed only after entering the code 4 The first available parameter appears on the display to select the ...

Page 23: ...sible to move the heat curve in parallel Each step corresponds to an increase 2 indoor probe only 421 Select the basic thermoregulation type according to the connected peripherals 832 Heat return temperature C When using the outdoor probe the boiler calculates the most suitable flow temperature taking into account the outdoor temperature and the type of installation 0 anti limescale stop at 67 C 0...

Page 24: ...crew the two screws on the front panel b pull it forward and detach it from the top hooks c d Before carrying out any operation on the boiler disconnect it from the power supply by closing the external bipolar switch and the gas valve 1 remove the crankcase by removing it from the housing a 24 b c a d MAINTENANCE Machine Translated by Google ...

Page 25: ...Switch on the appliance 4 As a result of the check in point 3 any disassembly and Turn off the water tap electrically disconnect the boiler and set the external bipolar switch to the OFF position close the gas tap and the water taps of the heating and plumbing installations provided The presence of oxide on the heat exchanger does not affect the performance of the boiler If you feel the need to cl...

Page 26: ...n gas category Periodically check the water pressure in the installation inform him about filling the installation with water and ventilating the radiators Performs according to the norms the maintenance operations of the installation 1 Brand 8 Installation type 17 Boiler power calibration 3 Mode Serial No 10 Maximum sanitary pressure 19 Usable gas 12 Boiler type 21 Maximum heating temperature 14 ...

Page 27: ...ific value of domestic hot water max min Pci Qn C 8 Min max heating temperature low temperature range 61 29 0 6 0 B23 B23p B33 Minimum ambient operating temperature C Minimum hot water flow Pa 22 97 5 88 0 0 7 0 03 3 A 108 3 97 5 24 EU kW 5 36 60 Excess air 80 C 60 C 5 24 4 5 9 Yield at rated calorific value 60 80 C Hi Hs Max power min 50 C 30 C Pn 230 50 36 60 Air pressure available 30 2 6 4 Weig...

Page 28: ...IARY CONSUMPTION OF ELECTRICITY Acoustic power level inside LWA HS PREMIUM EU gives ARISTON THERMO S p A 28 gives not 6 9 85 0 034 37 Template AN ITALIA Energy efficiency related to water heating ÿwh 88 1 OTHER PARAMETERS not Viale A Merloni 45 60044 FABRIANO 28 4 84 0 013 64 kW Yes No kW 24 EU ErP HEATING Daily electricity consumption Qelec Pstby standby heat loss gives not HS PREMIUM Boiler type...

Page 29: ...ng the seasonal energy efficiency class of the dual function heating system package temperature controller and solar device shall be at the same height as the arrowhead on the corresponding energy efficiency class 5 Indication 3 the class of seasonal energy efficiency related to the heating of the premises of the installation for heating the premises already loaded 4 the classes of seasonal energy...

Page 30: ...m the product sheet of the solar device for the declared load profile M L XL and XXL of the dual function heating installation I the value of the seasonal energy efficiency related to the heating of the premises of the heating installation with preferential double function expressed in III value of the mathematical expression Qaux 2 5 220 Qref expressed in where Qaux is taken from the product shee...

Page 31: ...other factors such as heat loss in the distribution system and product sizing in relation to the size and characteristics of the building Energy efficiency of water heating of the dual function heating system 2 I G 1 I 0 2 x AND Solar contribution From the saddle of the solar device Energy efficiency of water heating of the package in average climatic conditions C Energy efficiency classes related...

Page 32: ...Polona Street 1st Floor 010505 1st District Bucharest ITALIAN DESIGN Phone 004021 2319521 Fax 004021 2319510 e mail service ro aristonthermo com www ariston com ro Ariston Thermo Romania srl 199 111 222 Machine Translated by Google ...

Reviews: