![Argo ACS100 Service Manual Download Page 55](http://html.mh-extra.com/html/argo/acs100/acs100_service-manual_2967426055.webp)
1-
5
2
1
1-2. Major Component Specif cations
(A) Indoor Units
Concealed-Duct Type
ADS71PH
MODEL No.
ADS71PH
Source
220 - 230 - 240 V, 1 phase, 50/60 Hz
Controller P.C.B. Ass'y
CR-UXRP71B-B or CB-UXRP71B-B (Microprocessor)
Fan (Number...diameter, depth)
Centrifugal (3...ø190, L200)
Fan motor
Model...Nominal output
W
KFG4X-71B5P...70W
KFG4X-71D5P-S...70W
Source
220 - 230 - 240 V, 1 phase, 50/60 Hz
No. of pole...rpm (230V, High)
rpm
4P...1,063
Coil resistance
(Ambient temperature 20°C)
Ω
BRN–WHT : 74.72 ORG–YEL : 9.588
WHT–VLT : 19.14 YEL–BLK : 10.52
VLT–ORG : 10.52 BLK–PNK : 21.72
Safety device
Operation temperature
Open °C
130 ± 5
Operation temperature
Close °C
(115 ± 5)
Run capacitor
VAC, µF
450 VAC, 5.0 µF
Electronic expansion valve
Coil
–
Coil resistance (at 20°C)
Ω
–
Valve body
–
Heat Exchanger
Coil
Aluminium plate fin / Copper tube
Rows...fin pitch
mm
3...1.5
Face area
m
2
0.189
Panel
Model No.
–
Dew proof heater
–
Auto louver motor
–
Coil resistance (at 20°C)
Ω
–
Drain Pump
ADP-1413
PLD-12230STHU-1
Rated
VAC, W
AC 230V, 50Hz, 12W
Total head & capacity
500mm, 400cc/min
1200mm, 400cc/min
SM830159-06̲Elite̲PAC-i.indb 293
SM830159-06̲Elite̲PAC-i.indb 293
2012/04/27 15:22:20
2012/04/27 15:22:20