2-24. Test Run Procedure
Recheck the items to check before the test run.
(See 2-11)
Check the combination (wiring) of indoor and outdoor units.
(See 2-26-1)
YES
NO
(Automatic Address setting)
Turn ON the indoor
and outdoor power.
Set the indoor unit control unit to “TEST.
Can
operation be
started?
Refer to “Table of Self-
Diagnostic Functions” to
check the system.
In addition, refer to 2-26
and correct any items
that need to be corrected.
(See 2-13)
Note: Check the indoor-
side drainage.
NO
YES
NO
YES
(See 2-26-2) How to Set the Outdoor
Unit System Address
Set the outdoor unit system address.
(See 2-26-1, -2) How to Set Automatic Address
Set the automatic address setting from
outdoor unit.
(See 2-25)
(See 2-26-3)
(See 2-26-3, -4)
Is system “single-type”?
(1 indoor unit is connected to
1 outdoor unit)
Are multiple outdoor units
used?
Turn ON the indoor and
outdoor power.
(Automatic Address setting)
Indicate (mark) the combination number.
Turn the power back ON to the
indoor unit.
Fig. 2-22
System address rotary switch
System address 10s digit and 20s digit DIP switch
Automatic address button (black)
Terminal plug (black)
AES71PIH3E
TD (CN024, BLK)
TS (CN022, RED)
JP007
Terminal plug
(CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
EEPROM (IC007)
C2 (CN020, WHT)
C1 (CN021, WHT)
MOV(CN025, WHT)
AES100/125PIH3E
TO (CN023, BLK)
Fig. 2-21-b