2-15. Table of Self-Diagnostic Functions and Corrections (
AWS
Type)
Wired remote
controller
display
(Field supply)
Indoor unit
receiver lamp
Cause
Correction
1:1 connection (Single type)
Group connection
(Simultaneous
multi system)
Nothing is
displayed
Nothing is
displayed
• Indoor operation switch is OFF.
• Indoor unit power is not ON.
• Same at left.
Set the indoor operation switch ON.
Turn ON the indoor unit power.
E01 displayed
Operating lamp
is blinking.
• Automatic address setting has not
been completed.
• Inter-unit control wiring is cut or is not
connected correctly.
• Same at left.
• Check the inter-unit control wiring.
• Perform automatic address setting. (See
2-16.)
E14 displayed
–
• Remote controller
communication wiring
is cut or is not
connected correctly.
• Check the remote controller
communication wiring.
• Perform automatic address setting again.
E04 displayed
Standby lamp is
blinking.
• Indoor-outdoor inter-unit wiring is not
connected correctly.
• Same at left.
• Connect the wiring correctly.
E06 displayed
–
• Inter-unit control
wiring is cut or is not
connected correctly.
• Refer to 2-16 System Control, and make
the correct settings.
E15 displayed
• Indoor unit capacity is too low.
• Same at left.
• Check that the total capacities of the
indoor and outdoor units are appropriate.
E16 displayed
• Indoor unit capacity is too high.
• Same at left.
• Reverse 2 phases of the outdoor unit
3-phase power and connect them
correctly.
P05 displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
• Same at left.
• Connect the units correctly.
L02 displayed
Both the
Operation lamp
and Standby
lamp are blinking
simultaneously.
• Indoor-outdoor unit type mismatch.
• Same at left.
• Connect the units correctly.
L13 displayed
• Indoor-outdoor units are not setting
correctly.
• Same at left.
• Connect the units correctly.
L04 displayed
–
• Outdoor unit address
is duplicated.
• Connect the units correctly.
L07 displayed
–
• Remote controller
communication wiring
is connected to the
indoor unit, however,
it is set for individual
operation.
• Perform automatic address setting. (See
2-16.)
P15 displayed
Operation lamp
and Standby
lamp are blinking
alternately.
• No gas
• Same at left.
• Check the refrigerant cycle (for gas
leaks).
AES71PIH3E
Fig. 2-10-b
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
JP007
Te rminal plug (CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
EEPROM (IC007)
C2 (CN020, WHT)
C1 (CN021, WHT)
MOV(CN025, WHT)
AES100/125PIH3E
System address
rotary switch
System address
10s digit and
20s digit DIP switch
Automatic
address
button (black)
Terminal
plug (black)
SM830159-03̲Elite̲PAC-i.indb 12
SM830159-03̲Elite̲PAC-i.indb 12
2010/11/12 15:50:06
2010/11/12 15:50:06