1-
40
1
1-2. Major Component Specif cations
(A) Indoor Units
4-Way Air Discharge Semi-Concealed Type
ASS125PH
MODEL No.
ASS125PH
Source
220 - 230 - 240 V, 1 phase, 50/60 Hz
Controller P.C.B. Ass'y
CR-SXRP56B-B (Microprocessor)
Fan (Number...diameter, depth)
Turbo (1...ø460, 200)
Fan motor
Model...Nominal output
W
DK8-93C280H...90W
Source
280/340V (DC), 3-phase
No. of pole...rpm (230V, High)
rpm
8P...620
Coil resistance
(Ambient temperature 20°C)
Ω
RED–WHT : 43.0
WHT–BLK : 43.0
BLK–RED : 43.0
Run capacitor
VAC, µF
–
Safety device
overcurrent, rotating signal detection, fuse
Electronic expansion valve
Coil
–
Coil resistance (at 20°C)
Ω
–
Valve body
–
Heat Exchanger
Coil
Aluminium plate fin / Copper tube
Rows...fin pitch
mm
2...1.25
Face area
m
2
0.584
Panel
Indoor unit
Model No.
PNR-XD484GHAB (optional)
Dew proof heater
–
Auto louver motor
MP24GA
Coil resistance (at 20°C)
Ω
380 ± 7% / phase
Drain Pump
ADP-1414
Rated
VAC, W
AC230V, 50Hz, 12W
Total head & capacity
500mm, 400cc/min
SM830159-06̲Elite̲PAC-i.indb 277
SM830159-06̲Elite̲PAC-i.indb 277
2012/04/27 15:22:18
2012/04/27 15:22:18