– II-5 –
•
•
When Tc reaches 60
°
C or more, the current fan speed is
increased by one step.
When Tc reaches 35
°
C or less, the current fan speed is
decreased by one step.
Increases in fan speed are performed every minute after the fan speed changes.
Decreases in fan speed are performed every five minutes after the fan speed changes.
After the compressor is switched from on to off, the fan motor operates for 2 minutes 55
seconds at H or H+H speed.
SPW-CR484EL8 type
35
M+M
H+H
M+M
60
Tc(
°
C)
In low outdoor temperatures, the outdoor fan is set automatically from HIGH to LOW to
prevent the indoor heat exchanger from freezing.
When the outdoor temperature is less than 25.5
°
C, the outdoor fan is set from HIGH to
LOW automatically. When the outdoor temperature is 27.5
°
C or more, the outdoor fan is
set from LOW to HIGH automatically.
E Type