![Argo AC 425 C Technical Data & Service Manual Download Page 61](http://html.mh-extra.com/html/argo/ac-425-c/ac-425-c_technical-data-and-service-manual_2967424061.webp)
– I-59 –
TC
: Total Cooling Capacity
(kW)
SHC : Sensible Heat Capacity
(kW)
CI
: Compressor Input
(kW)
Rating conditions are
: Outdoor Ambient Temp. 35
°
C DB
: Indoor Unit Entering Air Temp. 27
°
C DB / 19
°
C WB
RATING CAPACITY :
12.6 kW
AIR FLOW RATE :
1920 CMH
EVAPORATOR
CONDENSER
ENT. TEMP.
°
C
AMBIENT TEMP
°
C
WB
DB
25
30
35
40
43
TC
12.00
11.53
11.05
10.61
10.33
CI
3.67
3.89
4.07
4.26
4.34
21
SHC
8.1
7.9
7.7
7.4
7.3
15
23
SHC
9.2
8.9
8.7
8.5
8.3
25
SHC
10.2
9.9
9.7
9.5
9.3
27
SHC
11.2
11
10.7
10.5
10.33
29
SHC
12
11.53
11.05
10.61
10.33
31
SHC
12
11.53
11.05
10.61
10.33
TC
12.85
12.34
11.83
11.35
11.06
CI
3.76
3.99
4.18
4.37
4.45
21
SHC
7.1
6.9
6.6
6.4
6.3
17
23
SHC
8.1
7.9
7.6
7.4
7.3
25
SHC
9.1
8.9
8.7
8.4
8.3
27
SHC
10.2
9.9
9.7
9.5
9.3
29
SHC
11.2
10.9
10.7
10.5
10.3
31
SHC
12.2
12
11.7
11.35
11.06
TC
13.68
13.14
# 12.6
12.10
11.78
CI
3.40
3.86
4.31
4.76
5.04
21
SHC
6
5.8
5.5
5.3
5.2
19
23
SHC
7
6.8
6.5
6.3
6.2
25
SHC
8
7.8
7.6
7.3
7.2
27
SHC
9.1
8.8
8.6
8.4
8.2
29
SHC
10.1
9.8
9.6
9.4
9.3
31
SHC
11.1
10.9
10.6
10.4
10.3
TC
14.52
13.95
13.37
12.84
12.50
CI
3.99
4.23
4.43
4.63
4.72
23
SHC
5.9
5.7
5.4
5.2
5.1
21
25
SHC
6.9
6.7
6.4
6.2
6.1
27
SHC
7.9
7.7
7.5
7.3
7.1
29
SHC
9
8.7
8.5
8.3
8.1
31
SHC
10
9.7
9.5
9.3
9.2
TC
15.38
14.77
14.16
13.60
13.24
CI
4.09
4.34
4.55
4.75
4.84
23
25
SHC
5.8
5.5
5.3
5.1
5
27
SHC
6.8
6.5
6.3
6.1
6
29
SHC
7.8
7.6
7.3
7.1
7
31
SHC
8.8
8.6
8.4
8.2
8
TC
16.23
15.59
14.94
14.35
13.97
CI
4.21
4.46
4.68
4.89
4.98
25
27
SHC
5.6
5.4
5.1
4.9
4.8
29
SHC
6.6
6.4
6.2
6
5.8
31
SHC
7.6
7.4
7.2
7
6.9
1-7
Cooling Capacity