– IV-4 –
4-2 Defective Sensor.
⁄
Indoor (heat exchanger) coil temp. Sensor is defective.
(a) Open (=No continuity in sensor)
Compressor and outdoor fan repeatedly go ON for 10 minutes and OFF for 6
minutes when sensor opens.
(b) Short
“Freeze Prevention” does not operate when dehumidified water is frozen on the
indoor coil.
¤
Room temp. Sensor (in the remote control unit) is defective.
(a) Open (=No continuity in sensor)
Neither the outdoor fan nor compressor runs.
(b) Short
The outdoor fan and compressor do not stop. — Excessive cooling.
4-3 Operation of Major Electrical Parts