![Argo AC 425 C Technical Data & Service Manual Download Page 115](http://html.mh-extra.com/html/argo/ac-425-c/ac-425-c_technical-data-and-service-manual_2967424115.webp)
– IV-10 –
(6)
Outdoor fan does not run.
• Check resistance of fan
motor winding.
• Check fan motor capacitor
OK
• Check continuity between
terminals on compressor
motor magnetic contactor.
• Check fan rotation.
Rotate fan gently once or
twice by hand.
• Check fan casing
for foreign matter
on the inside.
Remove foreign
matter or repair.
Repair or replace.
Fan cannot
be rotated.
• Fan motor burnout
or foreign matter
in bearing.
(8)
Compressor does not run.
• Check compressor motor capacitor.
Refer to
4-4
0635_X_S
• Check resistance of compressor motor winding.
• Check compressor motor overload relay.
OK
OK
OK
NG
NG
NG
Refer to
4-4
Refer to
4-4
Refer to 4-4
NG
Replace magnetic
contactor.
• Check continuity between terminals R-U, and
then S-V on the magnetic contactor.
OK
(7)
Outdoor fan speed is not switched from High to Low even when the outdoor
temperature falls below 25.5
°
C.
• Check thermostat (23S).
• Check coil resistance of
auxiliary relay.
(1Y)
0634_X_S