![Argo AC 425 C Technical Data & Service Manual Download Page 58](http://html.mh-extra.com/html/argo/ac-425-c/ac-425-c_technical-data-and-service-manual_2967424058.webp)
– I-56 –
TC
: Total Cooling Capacity
(kW)
SHC : Sensible Heat Capacity
(kW)
CI
: Compressor Input
(kW)
Rating conditions are
: Outdoor Ambient Temp. 35
°
C DB
: Indoor Unit Entering Air Temp. 27
°
C DB / 19
°
C WB
RATING CAPACITY :
7.3 kW
AIR FLOW RATE :
1080 CMH
EVAPORATOR
CONDENSER
ENT. TEMP.
°
C
AMBIENT TEMP
°
C
WB
DB
25
30
35
40
43
TC
6.95
6.68
6.40
6.15
5.99
CI
2.24
2.37
2.49
2.60
2.65
21
SHC
4.7
4.5
4.4
4.3
4.2
15
23
SHC
5.2
5.1
5
4.8
4.7
25
SHC
5.8
5.7
5.5
5.4
5.3
27
SHC
6.4
6.2
6.1
6
5.9
29
SHC
6.9
6.68
6.4
6.15
5.99
31
SHC
6.95
6.68
6.4
6.15
5.99
TC
7.45
7.15
6.85
6.58
6.41
CI
2.30
2.43
2.55
2.67
2.72
21
SHC
4.1
4
3.8
3.7
3.6
17
23
SHC
4.7
4.5
4.4
4.3
4.2
25
SHC
5.2
5.1
4.9
4.8
4.7
27
SHC
5.8
5.7
5.5
5.4
5.3
29
SHC
6.4
6.2
6.1
5.9
5.9
31
SHC
6.9
6.8
6.6
6.5
6.4
TC
7.93
7.61
# 7.3
7.01
6.83
CI
2.07
2.35
2.63
2.91
3.08
21
SHC
3.5
3.4
3.2
3.1
3
19
23
SHC
4.1
3.9
3.8
3.6
3.6
25
SHC
4.6
4.5
4.3
4.2
4.1
27
SHC
5.2
5
4.9
4.8
4.7
29
SHC
5.8
5.6
5.5
5.3
5.3
31
SHC
6.3
6.2
6
5.9
5.8
TC
8.41
8.08
7.75
7.44
7.24
CI
2.43
2.58
2.70
2.82
2.88
23
SHC
3.4
3.3
3.2
3
3
21
25
SHC
4
3.9
3.7
3.6
3.5
27
SHC
4.6
4.4
4.3
4.2
4.1
29
SHC
5.1
5
4.8
4.7
4.6
31
SHC
5.7
5.6
5.4
5.3
5.2
TC
8.91
8.56
8.21
7.88
7.67
CI
2.50
2.65
2.77
2.90
2.96
23
25
SHC
3.4
3.2
3.1
3
2.9
27
SHC
3.9
3.8
3.6
3.5
3.4
29
SHC
4.5
4.3
4.2
4.1
4
31
SHC
5.1
4.9
4.8
4.7
4.6
TC
9.40
9.03
8.66
8.31
8.10
CI
2.57
2.72
2.85
2.98
3.04
25
27
SHC
3.3
3.1
3
2.9
2.8
29
SHC
3.8
3.7
3.6
3.4
3.4
31
SHC
4.4
4.3
4.1
4
3.9
1-7
Cooling Capacity