Instruction manual
–
AQ G3x7 Generator protection IED
208 (211
)
7.5
T
ESTS AND ENVIRONMENTAL CONDITIONS
7.5.1
D
ISTURBANCE TESTS
EMC test
CE approved and tested
according to EN 50081-2,
EN 50082-2
Emission
- Conducted (EN 55011 class A)
- Emitted (EN 55011 class A)
0.15 - 30MHz
30 - 1 000MHz
Immunity
- Static discharge (ESD) (According to
IEC244-22-2 and EN61000-4-2, class III)
Air discharge 8kV
Contact discharge 6kV
- Fast transients (EFT) (According to
EN61000-4-4, class III and IEC801-4,
level 4)
Power supply input 4kV,
5/50ns
other inputs and outputs
4kV, 5/50ns
- Surge (According to EN61000-4-5
[09/96], level 4)
Between wires 2 kV /
1.2/50
μs
Between wire and earth 4
kV / 1.2/50
μs
- RF electromagnetic field test
(According. to EN 61000-4-3, class III)
f = 80
….1000 MHz 10V /m
- Conducted RF field (According. to EN
61000-4-6, class III)
f = 150 kHz
….80 MHz 10V
7.5.2
V
OLTAGE TESTS
Insulation test voltage acc- to IEC 60255-
5
2 kV, 50Hz, 1min
Impulse test voltage acc- to IEC 60255-5
5 kV, 1.2/50us, 0.5J
7.5.3
M
ECHANICAL TESTS
Vibration test
2 ... 13.2 Hz ±3.5mm
13.2 ... 100Hz, ±1.0g
Shock/Bump test acc. to IEC 60255-21-2
20g, 1000 bumps/dir.
7.5.4
C
ASING AND PACKAGE
Protection degree (front)
IP 54 (with optional cover)
Weight
5kg net
6kg with package