Instruction manual
–
AQ G3x7 Generator protection IED
151 (211
)
Figure 3-90: IEEE standard dependent time characteristics
The maximum delay time is limited by the parameter VPH24_MaxDel_TPar_ (Max.Time
Delay). This time delay is valid if the flux is above the preset value VPH24_EmaxCont_IPar_
(Start U/f LowSet).