Instruction manual
–
AQ G3x7 Generator protection IED
101 (211
)
If the parameter setting requires also a trip signal (DOP32_StOnly_BPar_=0), then the
measurement of the definite time delay is started. The expiry of this timer results in a trip
command.
The symbol of the function block in the AQtivate 300 software
The function block of directional overpower protection function is shown in figure below. All
binary input and output status signals applicable in the AQtivate 300 software are explained
below.
Figure 3-61: The function block of the directional over power protection function.
Table 3-39 Setting parameters of the directional overpower protection function.
Parameter
Setting value, range
and step
Description
Operation
Off
On
Operating mode selection for the function. Operation can be
either disabled
“Off” or enabled “On”.
Default setting is
enabled.
Start signal
only
Activated
Deactivated
Selection if the function issues either “Start” signal alone or
both “Start” and after set time delay “Trip” signal.
Default is
that both signals are generated (=deactivated).
Direction
angle
-
179…180
by step of
1
Power direction angle setting, angle between P and Q.
Default setting is 0
Start power
1
…
200% by step of
0.1.
Minimum power setting. Default setting is 10.
Time delay
0
…
60000ms by step
of 1.
Definite time delay of the trip command. Default setting is
100.