Instruction manual
–
AQ G3x7 Generator protection IED
163 (211
)
Figure 3-2 Example picture where two I> TOC51 and I0> TOC51N trip signals are
connected to two trip logic function blocks.
In this example we have a transformer protection supervising phase and residual currents
on both sides of the transformer. So in this case the protection function trips have been
connected to their individual trip logic blocks (for high voltage side and low voltage side).
After connecting the trip signals into trip logic block the activation of trip contacts have to be
assigned. The trip assignment is done in Software configuration
→
Trip signals
→
Trip
assignment.
Figure 3-3 Trip logic block #1 has been assigned as HV side trip to activate trip contact E02.
Trip logic block #2 has been assigned as MV side trip to activate trip contact E04.
The trip contact assignments can be modified or the same trip logic can activate multiple
contacts by adding a new trip assignment.