Instruction manual
–
AQ G3x7 Generator protection IED
203 (211
)
100% stator earth-fault protection U0
f3
>, (64F3)
Pick-up starting inaccuracy
< 0,5 %
Reset time
U>
→
Un
U>
→ 0
50 ms
40 ms
Operate time inaccuracy
+ 15 ms
Reset ratio
1.1
Underimpendace protection function Z< (21)
Current effective range
20 - 2000% of In
Voltage effective range
2 - 110% of Un
Impedance effective range
In= 1A
In=5A
0.1 - 200 Ohm
0.1
–
40 Ohm
Zone static inaccuracy
48
–
52Hz
49.5
–
50.5Hz
±5%
±2
%
Zone angular inaccuracy
±3°
Operate time
Typically 25ms
Operate time inaccuracy
±
3% or 15ms
Minimum operate time
<20ms
Reset time
16
–
25ms
Reset ratio
1.1
Loss of field protection function X< (40Z)
Current effective range
20 - 2000% of In
Voltage effective range
2 - 110% of Un
Impedance effective range
In= 1A
In=5A
0.1 - 200 Ohm
0.1
–
40 Ohm
Impedance calculation angular inaccuracy
±3°
Instant operate time
Typically 25ms
Operate time inaccuracy
±
3% or 15ms
Minimum operate time
<20ms
Reset time
16
–
25ms
Reset ratio
1.1