5.2 Arc light and pressure point sensor AQ-02
AQ-02 is an arc light and pressure point sensor that comes with arc light detection and ambient
pressure detection. The AQ-02 sensors should be mounted in the switchgear cubicles in such a way
that the light-sensitive part covers the protected area as completely as possible. Only one sensor
should be used per one closed metal-clad compartment. The AQ-02 sensors ccanno
annott be installed in
open spaces.
The default light intensity threshold for an AQ-02 sensor is 8,000 lux. Depending on the demand of the
application, the default threshold can also be set to 25,000 lux or 50,000 lux. An arc light sensor does
not require further settings by the user. Its detection radius is 180 degrees. The pressure threshold is
fixed at 0.2 bar above ambient pressure.
Figure. 5.2 - 24. AQ-02 arc light and pressure point sensor.
An AQ-02 can only be installed on the compartment wall as not to block pressure detection located
next to "the eye". The unit placed on the wall (with the gray side against the wall), and then fixed to the
wall with two screws. No external mounting plates are needed regardless of the mounting type;
however, mounting brackets can be used if so desired.
Up to three (3) sensors can be connected in series. Installing a connection cable is simple as each end
of the sensor has a detachable cover over the cable connectors. Please remember to reattach the
cover once the wires have been installed.
5.3 Sensor—unit dependencies
Different sensor types can be used with different arc flash protection units of the AQ-100 series. The
table below describes those dependencies.
Table. 5.3 - 5. Sensor—unit dependencies.
A
AQ
Q-01
-01
A
AQ
Q-02
-02
A
AQ
Q-06
-06
A
AQ
Q-07
-07
A
AQ
Q-08
-08
A
AQ
Q-101
-101
Yes
Yes
Yes (when the unit is
equipped with the fiber
option)
Yes (when the unit is
equipped with the fiber
option)
Yes (when the unit is
equipped with the fiber
option)
A
AQ
Q-101D
-101D
Yes
Yes
Yes (when the unit is
equipped with the fiber
option)
Yes (when the unit is
equipped with the fiber
option)
Yes (when the unit is
equipped with the fiber
option)
A
AQ
Q-101S
-101S
Yes
Yes
No
No
No
A
AQ
Q-102
-102
No
No
Yes
Yes
Yes
A
AQ
Q-103
-103
Yes
Yes
Yes (when the unit is
equipped with the fiber
option)
Yes (when the unit is
equipped with the fiber
option)
Yes (when the unit is
equipped with the fiber
option)
A
AQ
Q-101S
-101S
Instruction manual
Version: 2.01
24
© Arcteq Relays Ltd
IM00007
Summary of Contents for AQ-101S
Page 1: ...AQ 101S Arc flash protection unit Instruction manual ...
Page 2: ......