Table. 4.4 - 4. DIP switch settings.
PPin number
in number
((name
name))
FFunction selection
unction selection
ON (le
ON (left position)
ft position)
OFF (
OFF (rig
right position)
ht position)
8
(L> or
or L> + I>)
The tripping criterion for the S2,
S3, S4 (sensor) and S5 (fiber)
channels.
Tripping on light only (L>).
Tripping on light and overcurrent
(L> + I>), both of which are
required to occur simultaneously
to trigger tripping.
7
(S1: L> or
or L> +
I>)
The tripping criterion for the S1
sensor channel.
Tripping on light only (L>).
Tripping on light and overcurrent
(L> + I>), both of which are
required to occur simultaneously
to trigger tripping.
6
(Latch or
or Non-
latch)
Latching or non-latching for the
T1 and T2 trip relays.
T1 and T2 operate as latched.
T1 and T2 operate as non-
latched.
5
(100 ms or
or 150
ms)
The setting for the CBFP time.
The CBFP time is set to 100 ms.
The CBFP time is set to 150 ms.
4
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
3
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
2
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
1
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
NO
NOTE!
TE!
The T3 trip relays is always latched. The BO1 binary output function is always non-latched.
4.4.1 Scheme selection
This chapter describes the schemes that are available to this unit. The schemes are configured using
the DIP switches numbered 1…4 ("Scheme selection"). Most of the schemes are designed for double
busbar arc protection. For detailed instructions on each of the available schemes please refer to the
AQ-SAS™ booklet (can be found at
). Please note that there are four booklets: two
are for schemes based on IEC standards (MV and LV versions) and the other two for schemes based
on ANSI standards (MV and LV versions).
4.4.2 Available logic schemes
The schemes described below are the most important ones for this unit. However, additional schemes
are also available; please contact your nearest Arcteq representative for more information on
those schemes.
A
AQ
Q-101S
-101S
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
IM00007
15