11. If you are using the binary output signal and have configured it to send light information, verify
that it is activated.
12. Press the SET
SET push button to reset all indications and latches.
13. If you are using the BI2 binary input as the master trip, activate it and verify that the trip has
occurred by repeating the steps 5 and 6.
14. Press the SET
SET push button to reset all indications and latches.
15. Repeat the steps 1 through 15 for all sensors.
9.3 Testing the CBFP function
The circuit breaker failure protection (CBFP) function is tested by taking the light signal and the
secondary trip criterion signal (if applicable) and leaving them active for longer than the set CBFP time
(that is, 100 or 150 ms). The T2 trip relay and the BO1 binary output must be active after the set time
delay has passed to confirm the CBFP function operates correctly.
9.4 Testing the unit operation time
An operation time test is not required at commissioning as it is performed by the manufacturer both as
a type test and as a routine production test. If you want to have more information of these tests, please
refer to the routine test reports sent with the AQ-101S unit and/or consult your nearest Arcteq
representative for the type test reports.
However, if it is deemed necessary, you can conduct an on-site timing test with the following
instructions.
1. Use a calibrated relay test set.
2. Connect one of the test set's outputs to a strong camera flash to initialize the flash and to
configure the set's timer to start simultaneously with the flash.
3. Connect one of the AQ-101S unit's trip outputs (T1, T2, T3) to a test set input and configure
the input to stop the timer.
4. Place the camera flash within 20 cm (12 inches) of the sensor.
5. Initiate the flash and the timer by using the test set output.
6. Read the measured time between the simulated arc light and the operation of the trip
contact.
7. Subtract the digital input delay of the test set from the final measured time (if applicable). For
specific test instructions, please consult the manufacturer of the relay test set.
A
AQ
Q-101S
-101S
Instruction manual
Version: 2.01
32
© Arcteq Relays Ltd
IM00007