Conducted RF field
(EN 61000-4-6, level 3)
f = 150 kHz…80 MHz, 10 V/m
11.10 Voltage tests
Table. 11.10 - 17. Technical data for the voltage tests.
Insulation test voltage (IEC 60255-5)
2 kV, 50 Hz, 1 min
Impulse test voltage (IEC 60255-5)
5 kV, 1.2/50 µs, 0.5 J
11.11 Mechanical tests
Table. 11.11 - 18. Technical data for the mechanical tests.
Vibration test
2…13.2 Hz (± 3.5 mm)
13.2…100 Hz (±1.0 g)
Shock/bump test (IEC 60255-21-2)
20 g and 1,000 bumps/dir.
11.12 Environmental conditions
Table. 11.12 - 19. Technical data for the environmental conditions.
Specified ambient service temperature
–35…+70 ºC
Transportation and storage temperature
–40…+70 ºC
Relative humidity
Up to 97 %
Altitude
Up to 2,000 m above sea level
11.13 Casing
Table. 11.13 - 20. Technical data for the device casing.
Protection:
- front
- back
IP 50
IP 20
Device dimensions (W × H × D)
50 × 177 × 161 mm
Weight
0.7 kg
A
AQ
Q-101S
-101S
Instruction manual
Version: 2.01
38
© Arcteq Relays Ltd
IM00007