Aqualisa Quartz Electric Installation And User Manual Download Page 13

13

INSTALLATION

Pipework 

1   

Carefully remove the red outlet plug assembly. 
Note: Water will be present in the unit due to 
production testing.

In addition to the guide below it is essential that the written instructions
overleaf are read and understood and that you have all the necessary
components (shown overleaf) before commencing installation. Failure to
install the product in accordance with these instructions may adversely affect
the warranty terms and conditions. Do not undertake any part of this
installation unless you are qualified to do so. Prior to starting, ensure that
you are familiar with the necessary plumbing and electrical regulations and
legislation required to install the product correctly and safely.

The Quartz Electric is supplied with universal fittings intended to secure the
unit to a suitable wall.

Carefully remove the red outlet plug assembly. 

1

Pipe work installation

Mains voltage connection

Remove the securing screws at the top and bottom

of the Quartz Electric front casing and carefully lift

the casing away from the back plate assembly.

Carefully detach the solenoid connector and pull

the front casing clear.   

2

Hold the cover next to the shower unit on

the wall and carefully attach the two sole-

noid connectors. Place the solenoid connec-

tor block into the saddle within the shower

unit and neatly tuck the wires into the

recess provide. 

With the self tapping screws partially fitted

to the fixing locations in the front casing,

carefully offer it onto the back plate

assembly ensuring the wires are not

trapped. The control knob, in the fully cold

position, may have to be slightly adjusted

to enable the keyways to align. 

5

6

!

This shower must be fully commissioned following the procedure detailed
below before use. Failure to do so could damage the shower and invalidate
the guarantee. 

Front cover installation and shower commissioning

!

Front cover preparation

The installation must be earth bonded in accordance with current regulations

Where earth bonding of the premises is not evident, it may be necessary to
run bonding cable back to the earth terminal at the consumer unit.

!

Attach the hose to the shower handset as detailed above after passing it

through the hose restraint/gel hanger (if required) and place in the handset

holder in a position where it can spray safely. Push the solenoid piston up until

water sprays through the handset for a few seconds before releasing the

piston.

3

Turn the flow control valve on the shower

unit to the full cold (6 o’clock position). Turn

the flow control lever on the front casing to

the full cold position (9 o’clock). The flow

control valve and lever are keyed and must

be correctly positioned in order for the cover

to fit. 

4

Secure the front cover to the base plate

using the 3 fixing screws taking care not to

overtighten. 

7

Turn the flow control knob to ensure it moves smoothly. If not, the knob may

be fitted incorrectly. The shower should be commissioned with the knob in

the mid position (12 o’clock).

8

Slowly turn the flow control knob towards the hot direction. The heater

elements should now be hotter and the temperature of the spray should

increase.

10

When the unit is fully commissioned please remove the red warning label

from the front of the shower casing.

12

Adjust the flow control knob to provide the desired temperature. Allow a few

seconds after each adjustment for the temperature to stabilise. A cool shower

can be achieved with the flow control knob set towards the cold direction.

The temperature achieved will depend on the incoming water temperature

and pressure.

11

Turn on the electrical isolation switch. Press the start stop button and ensure

the blue light surround illuminates.

9

Quartz

Electric

®

BEFORE ANY ELECTRICAL CONNECTION IS ATTEMPTED, THE ELECTRICITY
SUPPLY MUST BE TURNED OFF AT THE MAIN SWITCH. FAILURE TO DO SO
COULD RESULT IN ELECTROCUTION.

The electrical installation should be carried out by a qualified person in
accordance with IEE (Institution of Electrical Engineers) wiring regulations
(BS 7671).

THIS APPLIANCE MUST BE EARTHED.

IN THE INTERESTS OF ELECTRICAL SAFETY, A 30mA RESIDUAL CURRENT
DEVICE (RCD) MUST BE INSTALLED IN ALL UK 230-240V ELECTRIC 
SHOWERS AND PUMPED CIRCUITS. THIS MAY BE PART OF A CONSUMER
UNIT OR A SEPERATE UNIT.

A suitably rated double-pole isolating switch for supply disconnection must
be incorporated in the fixed wiring circuit in accordance with current wiring
rules. This must have a mechanical indicator showing when the switch is in
the OFF position. A neon lamp alone is not sufficient. (See the electrical
rating chart for minimum switch rating). If it is fitted in the bathroom it must
be the cord-operated type. The switch must be readily accessible and clearly
identifiable in zone 3, i.e. at 0.6metres horizontally from the shower cubicle or
edge of the bath, or located above zone 2 (i.e. adjacent to the shower cubicle
or bath, but at least 2.25metres from the floor) as detailed below. This
requirement does not apply to the pull cord from the switch.

Where shower cubicles are located in rooms other than bathrooms, any
socket outlet in the room must be situated at least 3 metres from the shower
cubicle and protected by 30mA RCD.

!

Electrical installation

Wiring installation

Shower head installation

Earth bonding

Electrical rating

The shower unit must only be connected to a 230-240V ac supply.

1

Replace the service tunnel and secure using the fixing screw provided. 

2

The shower unit must be connected to its own independent electrical circuit. It

MUST NOT be connected to a ring main, spur, socket outlet or lighting circuit,

otherwise the circuit will overheat..

3

Pipe work connection must be made using a 15mm

compression elbow for top, bottom or rear entry (not

supplied). A copper olive is supplied located on the

shower inlet stub and should be fitted into the

compression elbow prior to the elbow being connected. 

7

Rear entry

The wall must be sufficiently chased out around the pipe and cable to allow

room for the nut on the compression elbow to be recessed into the wall. The

pipe work must be connected to the elbow prior to fitting the shower unit to

the wall. 

!

The shower head should be sited close to the shower unit, not necessarily on the same

wall, but not so that the unit is subjected to continuous spray. The shower head should

be sited so that it is no more than 610mm (2ft) above the bottom of the unit or no lower

than 305mm (1ft) below the unit, when in its normal position in the shower head holder. 

! THE SHOWER OUTLET, HOSE AND HANDSET ACT AS A VENT. THEY MUST NOT BE

BLOCKED, OBSTRUCTED OR HAVE CONNECTED TO THEM ANY FITTING NOT

APPROVED BY US. THE USE OF UNAPPROVED ACCESSORIES MAY INVALIDATE THE

GUARANTEE AND MAY AFFECT THE PERFORMANCE AND SAFETY OF THE UNIT.

When the pipe work and electrical connections have been completed the front cover can

be prepared to be fitted prior to beginning the commissioning procedure.

! THE TENSION OF THE HANDSET STATION OF THE

HANDSET HOLDER IS FACTORY SET. HOWEVER, IT

MAY BE NECESSARY, TO TIGHTEN THE TENSION AS

REQUIRED. TIGHTEN THE SCREW INSIDE THE

HANDSET STATION TAKING CARE NOT TO

OVER-TIGHTEN. 

Prepare two fixing points 465 – 470mm vertically apart using the fixings

provided, if suitable. 

1

If the consumer unit has a rating below 80A or if there is no spare fuse way,

then the installation will not be straightforward. It may be necessary to install

a new consumer unit to service the whole house or just the shower. This

should be installed by a qualified person. It may be necessary to contact the

electricity supplier to upgrade the incoming supply. 

5

Pass the rail through the handset holder

whilst keeping the slider button depressed. 

2

To comply with current water supply regulations,

the handset should not be able to pass a point

25mm above the spill over level of the bath or

tray. If this is not achieved, then the hose

restraint/gel hanger must be used Slide this

onto the rail under the handset holder. 

3

If using top or bottom entry pipe work connection, fix the unit to the wall

using the screws provided, if suitable.

5

Before making electrical connections within the installation make sure that no

terminal is live. If in doubt, switch off the whole installation at the consumer

unit or switch fuse (where fitted).

2

Secure the rail assembly to wall using the fixings provided, if suitable,

ensuring the rail and rail end bodies remain firmly engaged. 

Please complete the commissioning procedure detailed below prior to connecting the
handset and hose.

5

Flush through the water supply pipe allowing it to discharge safely to

waste.

6

Carefully unscrew and remove the service

tunnel and set aside. (This may be required if

retrofitting this shower to an existing shower

site). 

3

Tape the template provided onto the finished wall

surface in the desired position and mark the 3 fixing

points. Drill and prepare the fixings holes using the

fixing kit provided, if suitable. 

4

Turn on the water supply to the shower unit and check for leaks up stream of

the shower unit. If all is sound turn off the water supply to the shower unit.

8

Refer to the electrical rating diagram (shown overleaf) to determine the nominal current

of the shower. The current rating of the supply cable must be at least that of the shower

itself. Use the rating chart to choose a fuse or mcb with a rating of less than that of

your chosen cable. 

! WE STRONGLY RECOMMEND NOT USING REWIRABLE FUSES.

The current rating will be reduced if the cable is to be:

A. Bunched with others

B. In an ambient temperature above 40ºC

C. In an insulating wall or within thermal insulation, e.g. loft insulation.

D. In any other unusual position

If in doubt about any aspect of electrical installation, consult a qualified electrical

engineer or the electricity supplier.

Aqualisa reserves the right to revoke the terms of the warranty should access

to service connections be denied by the use of solid setting infill material. 

Please refer to the typical system diagram opposite.

The following notes are for guidance only – the installation must comply with
current regulations.

!

Without fitting the shower head, fit the hose

washer into the hose and attach to the

shower outlet to allow the water to discharge

safely to waste.  

1

Ensuring the electric supply remains isolated

turn on the water supplies. Push the solenoid

piston up until water runs through and out of

the hose for a few seconds before releasing

the piston.  

2

Fit the rail into the rail end bodies taking care

to engage the location slot onto the lugs. 

4

Place the rail end caps into the rail ends and

push firmly into position. 

6

Remove the relevant pipe work and cable

entry point from the relevant section of the

front cover if required, using a suitable tool.

We recommend making good the cut out

section using a round file. Ensure the cover

fits over cables and pipe correctly. 

1

Fix the self tapping screws a couple of turns

into the fixing points at the top and bottom

of the unit to aid locating the fixing points

when securing the front casing to the back

plate. 

2

Ensuring the hose washers are in the correct

position, depress the anti-swivel locking 

button on the handset and secure the 

handset to the hose. Place the handset 

into the handset holder. 

7

Unclip the earth terminal block and reposition it into the holder on the

service tunnel.  

3

For most installations the removable service

tunnel will not be required, enabling the

earth connection to be made in the top right

hand corner of the unit as illustrated. 

1

If retro-fitting the unit to an existing shower

where the wiring cannot be connected as

above, it may be necessary to utilise the

service tunnel and alternative earth

connection position. 

!

Check that the consumer unit (main fuse box):

A has a main switch rating of 80A or above and B has a spare fuse way which will

take the fuse/mcb (miniature circuit breaker) you need to fit.

If so you can wire the shower direct to the consumer unit (please refer to the

typical system diagram below).

(Not all consumer units accept a 35/40/45A sized fuse).

4

Any cable MUST NOT have the outer insulation stripped back beyond the

bottom of back plate or service tunnel (if used) and must be protected from

water as shown. 

4

User Instructions

To turn on and set the temperature

1  Turn on the isolating switch. 

2  Press the start/stop button, the blue light ring should      

illuminate.

3  Rotate the control knob to give the desired temperature; 

clockwise for warmer and anticlockwise for cooler. Allow a 

few seconds after each adjustment for the temperature to 

stabilise. 

! WARNING: ALWAYS CHECK THE SHOWERING

TEMPERATURE BEFORE STEPPING INTO THE SHOWER.

IT WILL TAKE APPROXIMATELY 20 SECONDS TO REACH A STABLE TEMPERATURE.

To turn the shower off

1 Press the start/stop button.

2 Turn off your isolating switch.     

N.B. The phased shutdown feature of this shower requires the shower to run on for

a few seconds after the shower is turned off. This is a safety feature which flushes

any residual hot water out of the shower unit to protect the next user.

Shower head operation

! NEVER ATTEMPT TO MAKE ANY ADJUSTMENT TO THE

SHOWER HEAD BY PULLING ON THE SHOWER HOSE.

1 To select the preferred height for the shower head, depress 

the handset holder button fully to enable the slider to be 

moved up or down the rail. 

2 Angular adjustment is made by carefully but firmly pulling 

forwards or pushing back the shower head against the   

knuckle in the holder. 

3 To select the desired spray pattern rotate the shower spray 

plate clockwise or anti-clockwise. 

RCD (can be part of consumer unit)

Recommended
80A  or 100A
mains switch

Double pole isolating
switch - pull cord
or wall mounted in
accordance with
BS7671

Shower unit

Zone 0

Zone 0

Zone 2

Zone 2

Zone 2

Zone 2

Zone 1

Zone 1

Zone 3

Zone 3

Zone 2

Zone 1

Zone 1

Zone 2

Zone 2

Zone 2

Switch must
be outside
Zone 2

2.25m

2.25m

0.6m

0.6m

0.6m

0.6m

Switch must
be outside
Zone 2

If required, ensure the water pressure to the shower unit is within the

minimum and maximum requirements by following the pressure testing

procedure overleaf.

!

Quartz Electric update July 11.qxd:Aquavalve 700 Thermo.qxd  30/6/11  22:58  Page 2

2   

Remove the securing screws at the top and 
bottom of the Quartz™ Electric front casing and 
carefully lift the casing away from the back plate 
assembly. Carefully detach the solenoid connector 
and pull the front casing clear.

3   

Carefully unscrew and remove the service tunnel 
and set aside. (This may be required if retrofitting 
this shower in place of an existing one).

Summary of Contents for Quartz Electric

Page 1: ...QUARTZ ELECTRIC INSTALLATION AND USER GUIDE ...

Page 2: ...omponents 12 Installation 13 Pipework 13 Electrical Installation 15 Mains Voltage Connection 16 Electrical rating 18 Wiring Connection 18 Earth Bonding 20 Front Cover Preparation 20 Commissioning and Front Cover Installation 21 Shower Kit 23 Pressure and Flow Readings 26 User Instructions 27 Operating the Shower 27 Safety Maintenance and Care 27 Shower Head Operation 28 Cleaning and Maintenance 29...

Page 3: ...nected to the water mains and not connected by a hose set A suitable double pole isolation switch for supply disconnections must be incorporated in the fixed wiring circuit in accordance with current wiring rules See Electrical Installation section for further details This product must be installed by a competent person in accordance with all relevant current Water Supply Regulations ALL SHOWERS R...

Page 4: ...e chrome and Graphite Quartz Electric features an illuminated start stop button Quartz Electric s patented Over Temperature Protection OTP device ensures safer comfortable showering whilst the shower provides endless economical showering as it imposes no demand on stored hot water Aqualisa products are supplied complete with a 1 year guarantee that can be upgraded by registering the product with A...

Page 5: ... cable size mm Max cable run in m Installed in insulated wall 10 61 10 55 10 50 Conduit or trunking 6 37 10 55 10 50 Clipped direct or buried in uninsulated wall 6 37 6 33 10 50 Notes 1 Cable selection is dependant on de rating factors detailed in the electrical rating section 2 In certain installations the combination of low voltage and extended cable lengths may result in loss of power and a con...

Page 6: ... protected by a suitable approved conduit Before removing the shower heater cover ensure the heater is isolated from the electric mains Quartz Electric is suitable for household use only Flushing Some modern fluxes can be extremely corrosive and if left in contact will attack the working parts of this unit All soldering must be completed and the pipework thoroughly flushed out in accordance with c...

Page 7: ...unit or apply silicone The shower is spaced off the wall by integral pillars to allow air circulation around the unit The casing must not be sited where it is subjected to continuous spray from the shower head The Quartz Electric should not be sited in any situation where it is likely to freeze WARNING DO NOT SWITCH THE SHOWER ON IF THERE IS A POSSIBILITY THAT THE SHOWER COULD BE FROZEN If you hav...

Page 8: ...hower unit may cause the water pressure to drop below the minimum required This should therefore be taken into consideration The water inlet of this appliance shall not be connected to inlet water obtained from any other water heating system Pressure relief device PRD To meet European standards the shower unit features an integral pressure relief device PRD DO NOT operate the shower with a damaged...

Page 9: ...an at least every 2 years Cleaning the filter should only be completed by a qualified person Please refer to the instructions of how to clean the filter page 29 After installation Familiarise the end user with the operation of this product and hand them this guide Complete and post the guarantee card or register online at www aqualisa co uk Declaration of Conformity Aqualisa Products Limited decla...

Page 10: ...10 POSITIONING GUIDE This product must be installed by a competent person in accordance with all current Water Supply Regulations 165mm 25mm Approx 1 400mm 320mm A B 1 2 3 4a 4b 7 6 5 ...

Page 11: ...es are followed the pipework entry point for the shower will be approximately 1 400mm from standing level in the shower tray or bath 7 The depth height of the shower tray or bath must be taken into consideration when completing first fix To comply with water regulations building regulations or any specific local water company regulations and in accordance with BS EN 806 a double check valve should...

Page 12: ... white chrome Literature not shown Literature not shown g hile n the n 10 Check the reading on the pressure testing device is within the minimum and maximum requirements stated above 11 Isolate the water supply to the shower 12 Detach the pressure test device and remove the adaptor 13 Refit the filter assembly and secure using the fixings 14 Refit the pressure test adaptor into the fixing position...

Page 13: ... 2 Carefully unscrew and remove the service tunnel and set aside This may be required if retrofitting this shower to an existing shower site 3 Tape the template provided onto the finished wall surface in the desired position and mark the 3 fixing points Drill and prepare the fixings holes using the fixing kit provided if suitable 4 Aqualisa reserves the right to revoke the terms of the warranty sh...

Page 14: ...nnection must be made using a 15mm compression elbow not supplied for top bottom or rear entry A copper olive is supplied located on the shower inlet stub and should be fitted into the compression elbow prior to the elbow being connected IMPORTANT Do not use excessive force when making the connection to the unit Rear entry The wall must be sufficiently chased out around the pipe and cable to allow...

Page 15: ...VICE RCD SHOULD BE INSTALLED IN ALL UK 230 240V ELECTRIC SHOWERS AND PUMPED CIRCUITS THIS MAY BE PART OF A CONSUMER UNIT OR A SEPARATE UNIT A suitably rated double pole isolating switch for supply disconnection must be incorporated in the fixed wiring circuit in accordance with current wiring rules This must have a mechanical indicator showing when the switch is in the OFF position A neon lamp alo...

Page 16: ...ions 1 The shower unit must only be connected to a 230 240V AC supply 2 Before making electrical connections within the installation make sure that no terminal is live If in doubt switch off the whole installation at the consumer unit or switch fuse where fitted 3 The shower unit must be connected to its own independent electrical circuit It MUST NOT be connected to a ring main spur socket outlet ...

Page 17: ...5 If the consumer unit has a rating below 80A or if there is no spare fuse way then the installation will not be straightforward It may be necessary to install a new consumer unit to service the whole house or just the shower This should be installed by a qualified person It may be necessary to contact the electricity supplier to upgrade the incoming supply Typical system diagram Recommended 80A o...

Page 18: ...engineer or the electricity supplier Wiring i For most installations the removable service tunnel will not be required enabling the earth connection to be made in the top right hand corner of the unit as illustrated 1 Loosen the terminal block screws and insert the wires as indicated on the back plate moulding IMPORTANT Ensure that the terminal block screws are fully tightened and that no cable in...

Page 19: ... and reposition it into the holder on the service tunnel 4 Any cable MUST NOT have the outer insulation stripped back beyond the bottom of back plate or service tunnel if used and must be protected from water as shown Refer to the indicator guide on the service tunnel The service tunnel MUST NOT be cut or altered in any way ...

Page 20: ...correctly Front cover installation and shower commissioning Front cover preparation When the pipe work and electrical connections have been completed the front cover can be prepared to be fitted prior to beginning the commissioning procedure THE TENSION OF THE HANDSET STATION OF THE HANDSET HOLDER IS FACTORY SET HOWEVER IT MAY BE NECESSARY TO TIGHTEN THE TENSION AS REQUIRED TIGHTEN THE SCREW INSID...

Page 21: ...he water to discharge safely to waste 2 Ensuring the electric supply remains isolated turn on the water supplies Push the solenoid piston up until water runs through and out of the hose for a few seconds before releasing the piston 3 Turn the flow control valve on the shower unit to the full cold 6 o clock position Turn the flow control temperature dial on the front casing to the full cold positio...

Page 22: ...rtially fitted to the fixing locations in the front casing carefully offer it onto the back plate assembly ensuring the wires are not trapped The control knob in the fully cold position may have to be slightly adjusted to enable the keyways to align 5 6 Secure the front cover to the base plate using the 3 fixing screws taking care not to overtighten 7 Turn the flow control knob to ensure it moves ...

Page 23: ...e shower unit not necessarily on the same wall but not so that the unit is subjected to continuous spray THE SHOWER OUTLET HOSE AND HANDSET ACT AS A VENT THEY MUST NOT BE BLOCKED OBSTRUCTED OR BE CONNECTED TO ANY FITTING NOT APPROVED BY US THE USE OF UNAPPROVED ACCESSORIES MAY INVALIDATE THE GUARANTEE AND MAY AFFECT THE PERFORMANCE AND SAFETY OF THE UNIT 1 Prepare two fixing holes up to a maximum ...

Page 24: ...nt 25mm above the spill over level of the bath or shower tray If this cannot be achieved the hose must be passed through the gel hook which has also been designed to be utilised as a hose restraint 5 Secure the top rail bracket into position on the finished wall surface using the short wall screw 6 Slide the bottom rail bracket onto the bottom of the rail 7 Slide the rail assembly up through the t...

Page 25: ...ecure the bottom rail bracket to the wall using the long wall screw 9 Place the rail end caps into both brackets and push firmly into position 10 Pass the hose through the gel hook 11 Ensuring the hose washers are in the correct position depress the anti swivel locking button on the handset and secure the handset to the hose Place the handset into the handset holder ...

Page 26: ...minute Static pressure BAR Working pressure BAR This guide must be handed to the customer on installation completion The pressure test adaptor MUST be left with customer should future readings be necessary If static or working pressures are too low less than 0 9 Bar contact your local water authority Flow rate to be taken in the fully cold position with the shower head and hose attached ...

Page 27: ...fter each adjustment for the temperature to stabilise WARNING ALWAYS CHECK THE SHOWERING TEMPERATURE BEFORE STEPPING INTO THE SHOWER IT WILL TAKE APPROXIMATELY 20 SECONDS TO REACH A STABLE TEMPERATURE To stop the shower Press the start stop button IMPORTANT Turn off your isolating switch Note the phased shutdown feature of this shower requires the shower to run on for a few seconds after the showe...

Page 28: ...cy of the cleaning will vary according to the local water quality Symptoms because of a blocked or restricted shower handset include Shower temperature too hot and unable to obtain a cooler setting Temperature fluctuates from very hot to cold thermal cut out activating The shower will only function correctly with the hose and handset provided see shower head installation instructions Failure to do...

Page 29: ...should be cleaned using only a soft cloth and washing up liquid SIVE CLEANERS ement for chemical descaling in hard water areas the shower head incorporates rub clean d up that may occur in any of the holes can be broken down by gently rubbing the flexible g use This procedure should be completed regularly as often as once a week in some hard build up can affect the spray pattern and cause the show...

Page 30: ...re into place using the filter assembly fixing screws 6 Connect a pressure testing device not supplied to the adaptor 7 Ensuring the electrical supply remains isolated turn on the water supply to the shower 8 Push the solenoid piston up until water runs through to the shower unit 9 Check that the reading on the pressure testing device is within the minimum and maximum requirements stated above Rec...

Page 31: ...control knob is turned fully clockwise Turn flow control knob anticlockwise Water turned off at mains or servicing valve Ensure water is turned fully on at the mains and at servicing valve in supply SHOWER UNIT SUSPECTED OF BEING FROZEN If so DO NOT USE i Switch off immediately at electrical isolating switch ii Turn water off at servicing valve if fitted or at stop cock iii Contact our Customer Se...

Page 32: ...th a new hose b Ifthewaterdoesnotflow thereisablockageinthe plumbingtotheshower the filterortheshoweritself Contact our Customer Service Department if the shower is considered to be the problem Blocked inlet filter Remove the filter for inspection PLEASE REFER TO CLEANING AND MAINTENANCE SECTION Restricted operation of flow control knob Remove front cover and check operation of knob Flow adequate ...

Page 33: ...nd or hose blocked with scale or debris Clean the handset spray plate Remove hose and check for restrictions Run without the hose attached to check temperature Incoming main water pressure or flow too low After confirming that the filter is clear check with the installer or local water authority Seasonal conditions Warmer inlet water temperature Set temperature dial to coolest setting Note Seasona...

Page 34: ... main water devices are being used while showering Thermal cut out is operating normally making a click sound Increase the flow by turning the water control knob in the cold temperature direction anticlockwise Clean the handset and spray plate Over temperature protection device has activated Increase the flow by turning the water control knob in the cold temperature direction anticlockwise Clean t...

Page 35: ...35 ...

Page 36: ...f Aqualisa Products Limited Part No 438301 Issue 07 Sept 21 Aqualisa Products Limited The Flyers Way Westerham Kent TN16 1DE Aqualisa International Jan Palfijnstraat 26 002 Kortrijk Belgium 8500 Customer Helpline 01959 560010 Brochure Hotline 0800 652 3669 Website www aqualisa co uk Email enquiries aqualisa co uk Republic of Ireland Sales enquiries 01 864 3363 Service enquiries 01 844 3212 ...

Reviews: