LOW PRESSURE FAULT
ISSUE
The refrigerant system’s low-pressure switch is showing as open.
RESOLUTION
Heat Only Units
Place heat pump in heating mode and perform the following troubleshooting.
1. Check for proper fan operation. If the fan is not operating, contact AquaCal
®
Technical Support.
2. Check for obstructed airflow around the heat pump.
l
3. Check for a dirty or blocked evaporator coil.
l
4. Check for signs of heavy ice buildup on the coil.
Cool Only Units
Place heat pump in heating mode and perform the following troubleshooting.
Determine if an insufficient amount of water is being supplied to the equipment.
1. Confirm the filter pump is on.
2. If a multiple-speed filter pump is being used, run filter pump at a higher speed. Do not exceed the
maximum flow rate for the model.
3. Confirm water is not being diverted away from the heat pump.
l
l
Adjusting Water Flow Using ΔT (Delta-T)
Heat and Cool Units (Reversing)
Place heat pump in heating mode and perform the following troubleshooting.
1. Check for proper fan operation. If the fan is not operating, call for service.
2. Check for obstructed airflow around the heat pump.
l
3. Check for a dirty or blocked evaporator coil.
l
4. Check for signs of heavy ice buildup on the coil.
LP5 SYSTEM LOCKOUT
ISSUE
The heat pump has locked due to five low-pressure faults during one call for heating or cooling.
RESOLUTION
1. Deactivate then reactivate power to the heat pump to clear error.
2. Troubleshoot the low-pressure issue causing the error.
l
4
-
T
roubl
es
hoot
ing