CHAPTER 4
OPERATING INSTRUCTIONS
Entire Contents Copyright
2004 by Adaptive Power Systems, Inc. (APSI) • All Rights Reserved • No reproduction without written authorization from APSI.
APS-1000 Series
4 - 13
OM-001-01000-000-04.0
Unit Test Time.
Press the CURRENT
︿
or
﹀
buttons to step the current display between
SEC/Min/Hour.
Auto Loop.
Press the CURRENT
︿
or
﹀
buttons to step the current display between ×1,
×10, ×100. The total number of cycles of system output is determined by the number of loop
cycles set in the PROGRAM parameters “LooP CyCL” times the ratio (×1, ×10, ×100).
Frequency Hi Limit.
Press the CURRENT
︿
or
﹀
buttons to adjust the frequency limit
value in the current display within the available range: 45.0 – 500.0 Hz. This value sets the
upper frequency limit that can be adjusted during normal operation. The FrEq HI value must
be higher than the FrEq LO value.
Frequency Lo Limit.
Press the CURRENT
︿
or
﹀
buttons to adjust the frequency limit
value in the current display within the available range: 45.0 – 500.0 Hz. This value sets the
lower frequency limit that can be adjusted during normal operation. The FrEq LO value must
be lower than the FrEq HI value.
Voltage Hi Limit.
Press the CURRENT
︿
or
﹀
buttons to adjust the voltage limit value in
the current display within the available range: 0.0 – 300.0 V. This value sets the upper voltage
limit that can be adjusted during normal operation. The Volt HI value must be higher than the
Volt LO value.