803877 Rev. 00  

 
WALL THERMOSTAT OPERATION 

 

Heat 

Sets the unit into heating mode. 
Initiates heating when room 
temperature falls below set point.  

Off 

Disables heating and cooling 
modes, but allows control of fan. 

Cool 

Sets the unit into cooling mode. 
Initiates cooling when room 
temperature rises above set point. 

Auto 

(not shown) 

Found on automatic changeover 
thermostats only. Allows the 
thermostat to decide whether it 
should be in the heating or cooling 
mode. Usually a 4 F

 differential 

or “deadband” will exist between 
heating and cooling set points to 
prevent inadvertent rapid 
switching between modes. 

Temperature 
Setting

 

Establishes the “set point”, or 
desired room temperature. 

Fan On 

Synonymous with “Fan 
Continuous”. Fan will continue to 
run after the heating and cooling 
function has cycled off. Fan will 
continue to run even when mode 
switch is in Off position. 

Fan Auto 

Synonymous with “Fan 
Intermittent”. Fan will cycle on 
and off with the heating cycle or 
cooling cycle, and will not operate 
between cycles. 

 
ADDITIONAL FEATURES:

 

 
Some additional features of the Electronic Control 
units are as follows: 
 

Room Freeze Protection 

This feature is enabled when the unit is shipped from 
the factory. The feature can be disabled by qualified 
service personnel. If power is available to the unit, and 
regardless of whether it is turned ON or OFF, the unit 
will automatically supply heat to the room with the fan 
running at low fan speed if the room temperature falls 
to 50°F (10ºC). The heat will turn off when the room 
temperature reaches 55°F (13ºC). For the feature to 
work, the unit must be configured with an electric 
heater. The feature is enabled whether the unit is 
configured for keypad or remote thermostat. The 
protection remains active when the unit is OFF, for 

either keypad or remote thermostat application, as long 
as the unit is plugged in, power is available, and a heat 
source is configured in the unit and is working.  
 

Compressor Short-Cycle Protection 

If the electronic control shuts the compressor down for 
any reason, a 3 minute time delay will elapse before 
the compressor is allowed to re-start. This prevents 
compressor overload during re-start due to unequal 
system refrigerant pressures. 
 

Indoor Coil Freeze Protection 

Control of frost on the evaporator coil due to low 
indoor loads, or cold outdoor ambient temperatures, is 
provided.  
 
 

Low Outdoor Temperature Lock-out 

If the outdoor temperature is too low for proper 
compressor operation, cooling operation will be 
suspended until the outdoor temperature rises to an 
acceptable point, depending on the application.     
 

Indoor Temperature Limiting (Keypad Control 
Only) 

Using the keypad control and display, high and low 
temperature limits can be established to prevent the 
user from entering set point temperatures colder or 
warmer than what the property manager or hotel 
operator may desire. The temperature limit choices are 
as follows: 
 
Configuration Code 

Low Limit °F 
(ºC) 

High Limit °F 
(ºC) 

R1 

63            (17) 

86            (30) 

R2 

65            (18) 

86            (30) 

R3 

65            (18) 

90            (32) 

R4 

67            (19) 

88            (31) 

R5 

67            (19) 

92            (33) 

R6 

69            (20) 

90            (32) 

R7 

69            (20) 

72            (22) 

 
The procedure to set the limits is as follows: 
 
Depress the On/Off key, the °F/°C key, and the 
Warmer key simultaneously for 5 seconds to enter the 
limit setup mode. The Warmer and Cooler keys will 
scroll through the R-values indicated in the above 
table. Once the desired R-value has been obtained on 
the display, press the On/Off key to accept the change, 
and then press it again to effect the change and restore 
the normal display. 

Summary of Contents for NAEC SERIES

Page 1: ...PFLOW PACKAGED TERMINAL AIR CONDITIONER PTAC Cooling with Electric Heat INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Page 2: ...hout an air filter will void the warranty WARNING To avoid bodily injury ensure power is disconnected before removing the air filter as there will be potential exposure to rotating parts Always replace the air filter filter bracket and screw to close off the bottom of the unit to prevent unintended contact with the blower wheels before operating the unit Clean Coils As part of regular servicing cl...

Page 3: ... on the unit Rating Plate for the specific chassis Wire sizing must also take into account any distance from fuse box or breaker panel to receptacle to prevent excessive voltage drop in undersized wires IMPORTANT Low voltage to the unit will cause compressor starting problems and decrease the performance and reliability of the compressor BRANCH CIRCUIT PROTECTION The Current Rating of branch circu...

Page 4: ... chassis must be level from side to side and sloped toward the outdoors from front to rear in the order of 1 8 inch per foot once the chassis side flanges are drawn up tight to the wall sleeve using the four flange screws If the sleeve was originally installed with a slope in the bottom of the sleeve in the order of per foot downward from the indoor to outdoor side the chassis will still operate p...

Page 5: ...TART UP CHECKLIST Note Once the unit is installed it should be checked for proper function by qualified service personnel before turning it over to the User Circuit breakers wire size and electrical connections tight and correct Filter clean and properly in place Condenser air inlet and outlet free of obstructions and no short circuiting of condenser air Unit operated for 20 minutes to prove stabi...

Page 6: ...ds and then decreases room temperature by 1 degree for every subsequent press of the key F C Key This key toggles the display between Fahrenheit and Celsius temperature modes and affects all displayed temperatures Heat Key The Heat Key toggles the unit in and out of heating mode for every press of the key provided the On Off Key is ON Cool Key The Cool Key toggles the unit in and out of cooling mo...

Page 7: ...g A factory supplied 24 Volt wiring harness is provided with every unit to facilitate connection to the wall thermostat wiring One end has a multi pin connector which mates with a connector exiting the unit The other end has preinstalled butt splice connectors which play a dual role in insulating any unused connectors and can also be used to make the wire connections for wires that are used The fi...

Page 8: ...is detected at the location of the wall thermostat and is usually a much more accurate representation of bulk room temperature The thermostat used may have advanced features beyond the basic functions described below Consult your thermostat Installation and Operating Instructions for further information In addition to controlling room temperature the room thermostat is also used to select whether ...

Page 9: ...d whether the unit is configured for keypad or remote thermostat The protection remains active when the unit is OFF for either keypad or remote thermostat application as long as the unit is plugged in power is available and a heat source is configured in the unit and is working Compressor Short Cycle Protection If the electronic control shuts the compressor down for any reason a 3 minute time dela...

Page 10: ...only but it can be changed to open with low speed fan operation only by having qualified service personnel re wire the unit as shown on the specific wiring diagram affixed to the unit WARNING The conversion procedure involves exposure to high voltage electrical circuits in the control box in order to make the necessary change to the damper action tied to motor speed and must be performed by qualif...

Reviews: