803877 Rev. 00  

On/Off Key 

Each press of the key toggles the unit from an OFF 
state to an ON state or from an ON state to an OFF 
state. Heating and cooling functions, as well as the 
display, and all indicating LEDs except for the fan 
indicators, are enabled or disabled with this key.  When 
toggled OFF, the control preserves only two modes 
active; fan-only, and room freeze protection. 
 

Fan Key 

Each press of the Fan Key cycles the fan through three 
modes of operation; Low Speed, High Speed and Auto. 
Small green LEDs will indicate the mode. The On/Off 
key need not be ON to operate the fan and set fan 
speeds. Auto Mode will cycle the fan on and off, and 
determine the fan speed, in conjunction with the 
heating or cooling demand. 
 

Warmer Key 

Pressing the Warmer Key will cause the display to 
show the set point temperature for 3 seconds, and then 
increases room temperature by 1 degree for every 
subsequent press of the key. 
 

Cooler Key 

Pressing the Cooler Key will cause the display to show 
set point temperature for 3 seconds, and then decreases 
room temperature by 1 degree for every subsequent 
press of the key 
 

°F/°C Key 

This key toggles the display between Fahrenheit and 
Celsius temperature modes, and affects all displayed 
temperatures. 
 

Heat Key 

The Heat Key toggles the unit in and out of heating 
mode for every press of the key, provided the On/Off 
Key is ON. 
 

Cool Key 

The Cool Key toggles the unit in and out of cooling 
mode for every press of the key, provided the On/Off 
Key is ON. 
 
 

 

Figure 1 
 
 
OPERATION USING KEYPAD

 

 
When the unit is first plugged in, or when recovering 
from a power outage, there will be a random 5 to 15 
second delay before the electronic control powers up. 
This minimizes the large electrical surge that would 
otherwise occur if all units in a building started up at 
the same time.  
 

To Initiate Heating or Cooling Mode 

Press On/Off Key to turn on the LED display and 
commence full functionality. Push the °F/°C Key to 
obtain the desired temperature scale. Press the Heat or 
Cool key as applicable, and the current indoor 
temperature will be shown on the display. 
 

Set Desired Temperature 

Press Cooler or Warmer key as applicable. Each push 
of the key increases or decreases the set point 
temperature by 1 degree, as applicable. 

 
 
 

 
 
 
 
 
 
 
 
 

Summary of Contents for NAEC SERIES

Page 1: ...PFLOW PACKAGED TERMINAL AIR CONDITIONER PTAC Cooling with Electric Heat INSTALLATION OPERATION MANUAL IMPORTANT READ AND SAVE THESE INSTRUCTIONS INSTALLATION AND WIRING MUST BE IN ACCORDANCE WITH CEC NEC AND LOCAL ELECTRICAL CODES ...

Page 2: ...hout an air filter will void the warranty WARNING To avoid bodily injury ensure power is disconnected before removing the air filter as there will be potential exposure to rotating parts Always replace the air filter filter bracket and screw to close off the bottom of the unit to prevent unintended contact with the blower wheels before operating the unit Clean Coils As part of regular servicing cl...

Page 3: ... on the unit Rating Plate for the specific chassis Wire sizing must also take into account any distance from fuse box or breaker panel to receptacle to prevent excessive voltage drop in undersized wires IMPORTANT Low voltage to the unit will cause compressor starting problems and decrease the performance and reliability of the compressor BRANCH CIRCUIT PROTECTION The Current Rating of branch circu...

Page 4: ... chassis must be level from side to side and sloped toward the outdoors from front to rear in the order of 1 8 inch per foot once the chassis side flanges are drawn up tight to the wall sleeve using the four flange screws If the sleeve was originally installed with a slope in the bottom of the sleeve in the order of per foot downward from the indoor to outdoor side the chassis will still operate p...

Page 5: ...TART UP CHECKLIST Note Once the unit is installed it should be checked for proper function by qualified service personnel before turning it over to the User Circuit breakers wire size and electrical connections tight and correct Filter clean and properly in place Condenser air inlet and outlet free of obstructions and no short circuiting of condenser air Unit operated for 20 minutes to prove stabi...

Page 6: ...ds and then decreases room temperature by 1 degree for every subsequent press of the key F C Key This key toggles the display between Fahrenheit and Celsius temperature modes and affects all displayed temperatures Heat Key The Heat Key toggles the unit in and out of heating mode for every press of the key provided the On Off Key is ON Cool Key The Cool Key toggles the unit in and out of cooling mo...

Page 7: ...g A factory supplied 24 Volt wiring harness is provided with every unit to facilitate connection to the wall thermostat wiring One end has a multi pin connector which mates with a connector exiting the unit The other end has preinstalled butt splice connectors which play a dual role in insulating any unused connectors and can also be used to make the wire connections for wires that are used The fi...

Page 8: ...is detected at the location of the wall thermostat and is usually a much more accurate representation of bulk room temperature The thermostat used may have advanced features beyond the basic functions described below Consult your thermostat Installation and Operating Instructions for further information In addition to controlling room temperature the room thermostat is also used to select whether ...

Page 9: ...d whether the unit is configured for keypad or remote thermostat The protection remains active when the unit is OFF for either keypad or remote thermostat application as long as the unit is plugged in power is available and a heat source is configured in the unit and is working Compressor Short Cycle Protection If the electronic control shuts the compressor down for any reason a 3 minute time dela...

Page 10: ...only but it can be changed to open with low speed fan operation only by having qualified service personnel re wire the unit as shown on the specific wiring diagram affixed to the unit WARNING The conversion procedure involves exposure to high voltage electrical circuits in the control box in order to make the necessary change to the damper action tied to motor speed and must be performed by qualif...

Reviews: