background image

TROUBLESHOOTING GUIDE – REMOTE THERMOSTAT UNITS* 

SYMPTOM 

CAUSE 

CHECK / CORRECTION 

Unwanted source of heating or cooling is 
near the wall thermostat causing the 
thermostat to sense a temperature other 
than room temperature. 

Eliminate the unwanted heating or cooling source or move the 
wall thermostat. See if thermostat is too close to a supply air 
register. Seal the hole in the wall where the thermostat cable 
passes into the thermostat. 

Wall thermostat body may be heating up 
due to impingement of direct sunlight, at a 
certain time of day. 

Relocate thermostat, provide shade for the thermostat, or just 
live with the problem if it occurs for only a short time during 
the day. 

Thermostat does not 
Properly Control Room 
Temperature, Causes Unit 
to Run Continuously, or 
Causes Abnormal Cycle 
Times in Heating or 
Cooling Mode 

Defective thermostat. 

Test and replace if necessary. 

Low voltage. 

Check voltage with unit running and ensure it is within 
nameplate limits. 

Restricted condenser air. 

Check for dirt or other condenser coil restriction. Clean as 
necessary. 

Recycling of condenser air. 

Check for inadequate discharge air installation clearances. 
Coil not sealed against grille. Unit may not be completely 
pushed into sleeve 

Condenser fan motor operating 
intermittently, rotating slowly, or not at all. 

Check to see if fan or shaft is rubbing or experiencing external 
friction. Check free rotation of the motor shaft. Check voltage 
to the motor. Check motor capacitor. Check for miswiring. 
Motor may be seized internally. Motor may have open 
windings, or defective internal overload – if so, replace motor. 

Defective thermostat. 

Test and replace if necessary. 

Faulty or incorrect compressor overload. 

Check for correct overload model number and replace if 
incorrect. Otherwise, if running amps seem normal, replace 
overload. 

Indoor coil freezing. 

See “Indoor Coil Frosts” 

Compressor running too slow and drawing 
high amps. 

Compressor may be miswired. Check capacitor. Compressor 
may be seizing – if so, replace compressor. 

Indoor room temperature too cold. 

Compressor will cycle on and off by command of the indoor 
coil freeze protection device. 

Compressor Short Cycles 

Outdoor temperature too cold. 

Compressor is not intended to operate at cold outdoor 
temperatures. Compressor will cycle on and off by command 
of the indoor coil freeze protection device. 

System switch set OFF on wall thermostat 

Switch to COOLING  

Fuse or circuit breaker tripped. 

Replace or reset as necessary. 

Defective cooling relay. 

Test and replace if necessary. 

Defective switch. 

Test and replace if necessary. 

Defective thermostat. 

Test and replace if necessary. 

Indoor room temperature below thermostat 
set point. 

Lower thermostat setting if comfort not yet achieved. 

Indoor room temperature too cold. 

Compressor will cycle on and off by command of the indoor 
coil freeze protection device. 

Outdoor temperature too cold. 

Compressor is not intended to operate at cold outdoor 
temperatures. Compressor will cycle and then lock out by 
command of the indoor coil freeze protection device, until the 
outdoor temperature warms up.  

Broken, shorted, loose, or miswired wiring. 

Inspect and correct. 

Defective compressor capacitor. 

Test and replace if necessary. 

Defective compressor overload. 

Test and replace if necessary. 

Low voltage or no voltage to compressor. 

Check voltage and ensure it is within nameplate limits. 

Compressor windings open. 

Disconnect overload from compressor terminals. Check for 
winding resistance across all winding pairs C-S, C-R, S-R and 
check each terminal to the compressor shell for ground faults. 
Replace compressor if any windings are open-circuited or 
short circuited to the shell. 

Compressor Will Not Run 

Seized compressor. 

If all of the above check out OK and if pressures are 
equalized, and compressor draws high amps and will not 
start, compressor is seized and needs to be replaced. 

*This troubleshooting guide is intended for use by qualified service personnel.

Continued

Summary of Contents for DMQC Series

Page 1: ...rmostat depends on accurate room temperature sensing Be conscious of locating the thermostat where temperatures near the thermostat are not representative of room temperature For example do not install the thermostat where it is subjected to direct sunlight other sources of heat or cold drafts including air discharged from a supply air register A common error is not sealing the hole in the wall wh...

Page 2: ...cle and will not operate between cycles UNIT MOUNTED CONTROLS Dial Plate and Rotary Switch ROTARY SWITCH The rotary switch and dial plate are found under the control door which is located at the top right corner of the unit The knob can be rotated to the left or to the right of the Off position Heating output is not affected by fan speed The settings are addressed in the following table ROTARY SWI...

Page 3: ...nning too slow and drawing high amps Compressor may be miswired Check capacitor Compressor may be seizing if so replace compressor Indoor room temperature too cold Compressor will cycle on and off by command of the indoor coil freeze protection device Compressor Short Cycles Outdoor temperature too cold Compressor is not intended to operate at cold outdoor temperatures Compressor will cycle on and...

Page 4: ... Unit Rattles or is Noisy Rubbing of fan or blower on housing Ascertain cause and correct Check during operation System switch set OFF on wall thermostat Switch to HEATING Faulty thermostat Test and replace if necessary Fuse or circuit breaker tripped Replace or reset as necessary Cord not plugged in Plug in Defective switch Test and replace if necessary Defective heater Inspect and replace if nec...

Reviews: