background image

Professional Series Network Thermostat 
Configuration Guide

(NT100e/h, NT120e/h, NT130e/h, NT150e/h, and NT160)

Release 3.0 

Part No. 600-01000-200, Rev. 2
August 2007

Inside ...

„

Configuring the thermostat using the TDI

„

Configuring the thermostat using the TMI

„

Troubleshooting

Summary of Contents for Professional NT100e/h

Page 1: ...ermostat Configuration Guide NT100e h NT120e h NT130e h NT150e h and NT160 Release 3 0 Part No 600 01000 200 Rev 2 August 2007 Inside Configuring the thermostat using the TDI Configuring the thermostat using the TMI Troubleshooting ...

Page 2: ... of Proliphix Inc All other trademarks are the property of their respective owners This document contains information that is the property of Proliphix Inc This document may not be copied reproduced reduced to any electronic medium or machine readable form or otherwise duplicated and the information herein may not be used disseminated or otherwise disclosed except with the prior written consent of...

Page 3: ...ATIONS No Reverse Engineering Customer may not reverse engineer decompile or disassemble the SOFTWARE nor attempt in any other manner to obtain the source code No Separation of Components The SOFTWARE is licensed as a single product Its component parts may not be separated for use on more than one computer nor otherwise used separately from the other parts No Rental Customer may not rent or lease ...

Page 4: ...PTION LOSS OF BUSINESS INFORMATION OR ANY OTHER PECUNIARY LOSS ARISING OUT OF THE USE OF OR INABILITY TO USE THE SOFTWARE EVEN IF PROLIPHIX HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES OTHER If any provision of this LICENSE is inconsistent with or cannot be fully enforced under the law such provision will be construed as limited to the extent necessary to be consistent with and fully enforc...

Page 5: ...hich have all original and unaltered markings and labels serial numbers model numbers etc of manufacture This limited warranty does not cover the repair of cracked scratched broken or modified plastics other cosmetic damage or parts that have been altered defaced or removed or the scratching cracking or breakage of the product This warranty is not transferable THE FOREGOING WARRANTIES ARE THE SOLE...

Page 6: ...01886 The RMA number must be clearly marked on the outside of the package Products received without an RMA number or without shipping prepaid will be subject to refusal by Proliphix Proliphix reserves the right to charge a 15 restocking fee plus shipping costs on any products returned without an RMA Return shipping charges following repair of items under warranty shall be paid by Proliphix via sta...

Page 7: ...en 2 6 Sensor Status Screen 2 9 Status Control Screen 2 10 Thermostat Control Screen 2 11 Thermostat Status Screen 2 13 Alarm Status Screen 2 14 Network Status Screen 2 15 Installer Information Screen 2 16 Chapter 3 Configuring the Thermostat Using the TMI Thermostat Management Interface TMI Authentication 3 1 DHCP Assigned IP Addresses 3 2 Before you Begin 3 2 Connecting the Thermostat to the Loc...

Page 8: ...ngs Page 3 30 Advanced Settings Page 3 35 Sensor Settings Page 3 46 Remote Access Page 3 49 Remote Server Configuration 3 49 Alarm Notification 3 50 Remote Discovery Status Page 3 52 Installer Info Page 3 53 Usage Counters Page 3 54 Password Settings Page 3 56 Chapter 4 Troubleshooting Resetting the Thermostat 4 1 Software Reset 4 1 Factory Reset 4 2 ...

Page 9: ... 16 Figure 3 1 Status Control Login Page 3 7 Figure 3 2 Administrator or User Authentication Window 3 8 Figure 3 3 Status and Control Page 3 9 Figure 3 4 General Settings Alarms and Alerts Pending Page 3 14 Figure 3 5 Setback Schedules Page 3 19 Figure 3 6 Day Class Scheduling 3 20 Figure 3 7 NT150e h Occupied Unoccupied or Other Day Class Schedule Page 3 22 Figure 3 8 Default Weekly Schedule Page...

Page 10: ...formation Screen Options 2 16 Table 3 1 Thermostat Status Field Descriptions 3 10 Table 3 2 General Settings Field Descriptions 3 15 Table 3 3 Occupied Unoccupied or Other Class Schedule Field Descriptions 3 23 Table 3 4 Default Weekly Schedule Field Descriptions 3 24 Table 3 5 Network Settings Field Descriptions 3 31 Table 3 6 Advanced Settings Fields HVAC Fuel Burner Field Descriptions 3 37 Tabl...

Page 11: ...or managing multiple devices remotely in small or medium size buildings multiple buildings or corporate environments As a reader of this guide you should be familiar with the use of an Internet browser for example Internet Explorer or Mozilla Firefox and have a working knowledge of general data networking principles You should have prior experience with establishing a local area network LAN in eit...

Page 12: ...ription of each guide see Proliphix Documentation Library page xiii 1 2 3 Installing the Thermostat Proliphix Thermostat Installation Guide Proliphix Ethernet Power Adapter Installation Guide Refer to this manual only if you are installing an EPA 20 or EPA 60 Ethernet Power Adapter Connecting to the Local Network Professional Series Network Thermostat Configuration Guide Accessing the Thermostat R...

Page 13: ...uthentication at the Proliphix web site TM220e h and TM250e h Thermal Managment Series Network Thermostat Configuration Guide TM220e h and TM250e h For customer who want to access and control their Proliphix Thermal Management series thermostat through either the Thermostat Device Interface or more specifically through the browser based Thermostat Management Interface TMI NT100e h NT120e h NT130e ...

Page 14: ...for which you supply values courier italics Options and arguments for which you supply values Information that the user must enter Courier Bold font Screen messages or system output Courier Regular font Selecting a menu item Menu Option Book titles new terms and emphasized text Italics Note Additional information that may apply to the subject text Caution Proceed carefully to avoid possible equipm...

Page 15: ...del and serial number Type of heating cooling system for example gas oil or electric warm air hot water heat pump steam or gravity Location and number of wires attached to the Proliphix thermostat To contact Proliphix Technical Support Note Documentation is available for currently supported product releases Documentation is available in Adobe PDF format You can view PDFs online using the Adobe Rea...

Page 16: ...Preface Proliphix Welcomes Your Comments You can mail email or fax your comments Please include the document part number in the subject line of your email or fax message E mail techpubs Proliphix com Fax Attention Technical Publications 978 692 3378 Proliphix Inc Technical Publications 66 Tadmuck Road Suite 1 Westford MA 01886 ...

Page 17: ...stallers Authorized Proliphix Installers should consult the Proliphix Remote Management Setup Guide to learn how to properly administer and configure client thermostats for Remote Management The end user of the Professional Series Thermostats should consult the Proliphix Remote Management Setup Guide for a complete explanation of remotely managing your Network Thermostat Thermostat Model Humidity ...

Page 18: ...oliphix thermostats through your web browser Thermostat Device Interface The buttons on the front of the thermostat enable you to modify the temperature enable basic HVAC functions and to view the thermostat s network configuration and status Use the instructions in this guide to configure and manage your thermostat as shown in Figure 1 1 Figure 1 1 Thermostat Configuration Process Flow Chapter 2 ...

Page 19: ...ss and port number using the Thermostat Device Interface buttons and control on the front of the thermostat 1 From the Status Control Screen page 2 10 select the Network Status Screen page 2 15 and record the IP address and port number 2 Enter this IP address and port number address port_number as the URL in your web browser 3 Log in to the thermostat as the Administrator as follows Username admin...

Page 20: ...twork Thermostat Configuration Guide Release 3 0 Part No 600 01000 200 Rev 2 CHAPTER 1 Overview What s Next Continue with Chapter 2 Configuring the Thermostat Using the TDI or Chapter 3 Configuring the Thermostat Using the TMI to manage your thermostat ...

Page 21: ...nd screen options on the thermostat The thermostat s front panel includes up and down arrows and several buttons located at the bottom of the LCD to select the desired configuration settings Thermostat Buttons and LCD Screen Options This section describes the thermostat s buttons and LCD screen options Figure 2 1 shows the basic layout of all thermostat buttons and a typical LCD screen Figure 2 1 ...

Page 22: ...field in multi field screens Down arrow multiple uses screen sensitive Decreases the setpoint temperature settings Scrolls down one field in multi field screens Left button multiple uses screen sensitive Selects the function displayed on the LCD Middle button multiple uses screen sensitive Selects the function displayed on the LCD Right button multiple uses screen sensitive Selects the function di...

Page 23: ...Screen page 2 16 HVAC Screen page 2 6 Thermostat Control Screen page 2 11 Thermostat Status Screen page 2 13 Alarm Status Screen page 2 14 Network Status Screen page 2 15 Primary Screens Secondary Screens 1 2 3 4 Thermostat Control Type Back HVAC Type Fuel Burner Heat Ctrl 2H Cool Ctrl 2C Reset Thermostat Status Back Cool Apr 16 2007 8 30 PM Model Number NT 120 SW Version 3 0 00 HW Revision G 01 T...

Page 24: ... Table 2 2 Thermostat Screen Options Field Description Zone Name network host name Initially the Zone Name is set to the last six digits of the network MAC address e g 00 00 6A Button Lockout When visible indicates that some or all of the thermostat buttons are disabled from controlling the thermostat Alarm Indication When visible indicates that an alarm condition exists within the thermostat Alar...

Page 25: ...he schedule The Hold button toggles between Hold and Return See Advanced Settings Page on page 3 35 One Button Override OBO NT130e h and NT160e h only When Button Lockout is enabled this button allows you to set the thermostat to the Class 1 Day Period heat and cool setting as defined in the Setback schedule The amount of time that the One Button Override is in effect is determined by the setting ...

Page 26: ...hermostat Using the TDI HVAC Screen The HVAC screen is a sub screen of the default Thermostat Default Screen page 2 4 Most of the content on the HVAC screen is identical to the Thermostat screen with the exception of the HVAC mode and fan setting controls Figure 2 4 HVAC Screen Fan Setting and HVAC Mode Example Fan Control Fan State HVAC Mode HVAC Screen ...

Page 27: ...e Pages page 3 22 Auto The fan is controlled by either the heat or AC systems or both On Forces the fan to the on state independent of the heat or AC systems Fan Control Displays the options for changing the state of the fan See Fan State HVAC Mode Displays the options for changing the state of the HVAC System Auto Automatic changeover between the heat or A C systems Heat Enables the heating syste...

Page 28: ...e process of changing HVAC settings at the thermostat Figure 2 5 Changing the HVAC Setting 1 2 3 4 5 6 Select the middle HVAC button to enter the HVAC mode Select the middle Mode button to modify HVAC or fan settings Use the Down arrow to select Heat Press the middle Select button Press the right Back button to return to the default Thermostat screen Default Thermostat Status screen see Figure 2 3...

Page 29: ...tus Screens Table 2 4 lists the sensor status screen display options Note The NT100e h does not support external thermal sensors therefore this screen is not available on the NT100e h Network Thermostat Table 2 4 Sensor Status Screen Options Field Displays Zone Average Average temperature of any combination of Local Remote Sensor 1 e g East Entry and Remote Sensor 2 e g West Entry Rel Humidity NT1...

Page 30: ...ollowing four secondary screens from the Status Control screen Thermostat Control Screen page 2 11 Thermostat Status Screen page 2 13 Alarm Status Screen page 2 14 Network Status Screen page 2 15 Figure 2 8 Status Control Screen Table 2 5 lists the Status Control screen options Table 2 5 Status Control Screen Options Option Description Thermostat Control When highlighted and selected opens the The...

Page 31: ...een also displays the status of the selected type along with the default settings To change specific parameters for each type go to the Advanced Settings Page page 3 35 To initiate a software reset press the left button and see Resetting the Thermostat page 4 1 Figure 2 9 Thermostat Control Screen Thermostat Control Type Back HVAC Type Fuel Burner Heat Ctrl 2H Cool Ctrl 2C Reset Thermostat Control...

Page 32: ...aces Heat Pump SS Electric heat pump Single Stage HVAC system type Heat Pump DS O Electric heat pump Dual Stage O Rvs Valve HVAC system type Heat Pump DS B Electric heat pump Dual Stage B Rvs Valve HVAC system type See the Advanced Settings Page page 3 35 further explanation of the following parameters HVAC Type Displays the selected HVAC system type Fuel Burner or Heat Pump Fuel Burner Heat Ctrl ...

Page 33: ...Screen The Thermostat Status screen is a sub screen of the Status Control Screen page 2 10 This screen displays the following information for each thermostat Current date Product model number Software version Hardware revision Figure 2 10 Thermostat Status Screen Thermostat Status Back Cool Apr 16 2007 8 30 PM Model Number NT 120 SW Version 3 0 00 HW Revision G 01 ...

Page 34: ...lative Humidity has not dropped below the value set as the High Humidity Not OK Relative Humidity has dropped below the value set as the High Humidity Low Temp Limit Temperature below which an alarm indication is set by the thermostat OK Temperature of thermostat has not dropped below the value set as the Low Temperature Limit Not OK Temperature of thermostat has dropped below the value set as the...

Page 35: ... Screen The Network Status is a sub screen of the Status Control Screen page 2 10 This screen displays the following information Thermostat host name Unique Ethernet Media Access Control MAC address Internet Protocol IP address Web port number See Network Settings Page page 3 30 for more information on setting these parameters Figure 2 12 Network Status Screen ...

Page 36: ...mation screen is the fourth primary screen Figure 2 13 Installer Information Screen Table 2 8 lists the Installer Information screen options Table 2 8 Installer Information Screen Options Field Displays Company Name Installer company name Company Address 1 2 Installer address fields Company City State Province Zip Postal Code Installer city state province and zip postal code fields Company Telepho...

Page 37: ...ts requires password authentication prior to accessing the HTML pages that enable you to control or manage the thermostats There are two levels of authentication allowed to manage the Professional Series thermostats the Administrator account has the highest level of privileges and the User account has the lowest level of account privileges The username and password for each account is as follows A...

Page 38: ... router supports DHCP then your Proliphix thermostat automatically retrieves an IP Address Gateway Address and Subnet Mask from the DHCP server on your network Before you Begin Before you access the TMI to control and manage your thermostat complete the following prerequisite tasks described in this section Connect the thermostat to the network Obtain the device name default host name IP address a...

Page 39: ...Your thermostat s should automatically communicate with the local DHCP server and be assigned a unique IP address 2 Go to the physical location of each thermostat and record the following information using the worksheet below Use a separate piece of paper if necessary Information Thermostat 1 Thermostat 2 Thermostat 3 Device Name Zone Name of the thermostat Located in the upper left corner of the ...

Page 40: ...n to the TMI as the Administrator as follows Username admin Password admin default 2 Access the General Settings Page page 3 14 through the TMI 3 Enter a Device Name and Site Name for example the name or location of the property 4 Click Submit 5 Access the Network Settings Page page 3 30 6 Set the IP Address Method to Static and select a unique IP address Subnet Mask Gateway and HTTP port number 7...

Page 41: ... HTTP port number in your browser window For example http 192 168 111 100 80 Where 192 168 111 100 is a unique IP address initially assigned via DHCP and 80 is the default Proliphix assigned Web HTTP port number If you are upgrading your device from a previous version of Proliphix firmware this port number may be something other than 80 The old port number is carried forward after the firmware upg...

Page 42: ...ure on page 3 7 A yellow banner at the top of each page contains the following information for each thermostat Model number Page title Host name of the thermostat Each thermostat page also includes browser buttons which enable direct access to all other HTML pages on the thermostat The TMI displays each page in a table format Each feature table is organized by rows of functions in a left to right ...

Page 43: ...rol Login page appears Proliphix recommends that either the thermostat administrator admin or a user user log in to the thermostat from this page The thermostat s status is visible to either account without logging in but you must log in to control some of the parameters on this page Figure 3 1 Status Control Login Page Note In each TMI page you must click Submit to apply all changes made in the C...

Page 44: ...thentication Window 2 Enter the default username and password for the admin or user account as follows and click OK 3 Continue with the Status Control Page Field Admin Account User Account Username admin user Passworda a You can change passwords for each account using the Password Settings Page page 3 56 admin admin Note The Administrator can access all installer specific pages The User account is...

Page 45: ...ration Guide Release 3 0 3 9 Part No 600 01000 200 Rev 2 Status Control Page The TMI displays the default Status Control page after authentication The Status Control page displays a snapshot of most of the pertinent information accessible on the thermostat Figure 3 3 Status and Control Page ...

Page 46: ...perature averaging This field is not applicable on the NT100e h thermostat See Advanced Settings Page page 3 35 In a range of 30 F 34 C to 199 F 95 C RS 2 Displays the current temperature of Remote Sensor 2 if this remote thermal sensor is installed and enabled This field is disabled if RS 2 is not included in temperature averaging This field is not applicable on the NT100e h thermostat See Advanc...

Page 47: ...finitely or for a prescribed period of time as set on the Advanced Settings Page page 3 35 use the drop down menu and choose Hold Hold mode is enabled Off default Hold mode is disabled Schedule Settings Day Class Period Displays the current settings for both the scheduled Day Class and Period See Setback Schedules Page page 3 19 Cool Displays the current Cool temperature setting as set within the ...

Page 48: ...k Schedules Page page 3 19 Note When in Schedule mode the fan continues to work in Auto mode as well External Relay State NT150e h and NT160e h only Displays the current state of the External Relay Active The External Relay has been activated Inactive The External Relay is not active Alarm Status Low Temperature Displays the current status of the Low Temperature alarm condition The temperature has...

Page 49: ...imit before resetting this alarm See General Settings Alarms and Alerts Pending Page page 3 14 OK No High Humidity alarm exists Alert The humidity monitored within the thermostat has risen above the pre set high humidity threshold Filter Change Displays a reminder that the time interval between HVAC filter changes has expired The air filter s should be cleaned or replaced You should change the fil...

Page 50: ...600 01000 200 Rev 2 CHAPTER 3 Configuring the Thermostat Using the TMI General Settings Page The General Settings page contains parameters and settings that enable you to configure the thermostat name and location and set filter replacement reminders Figure 3 4 General Settings Alarms and Alerts Pending Page ...

Page 51: ...mperature scales Fahrenheit default All thermostat temperature readings and reporting are displayed in the Fahrenheit temperature scale F Celsius All thermostat temperature readings and reporting are displayed in the Celsius temperature scale C Backlight Select the LCD backlight control Delay default The backlight is illuminated when you click a button and remains illuminated for 16 seconds after ...

Page 52: ...If the current Zone Temperature falls below this value an alarm condition is set and the status is displayed on the Status Control Page page 3 9 In addition this alarm will be sent to the Proliphix web site to trigger an email notification if this function is Enabled Disable default No low temperature limit is set 30 F 34 5 C to 200 F 93 C This is a major red alarm condition Low Temp erature Dismi...

Page 53: ...e checked and the Zone Temperature must be below the High Temp Limit or the High Temp Limit must be set to Disable for the alarm condition to be cleared upon a Submit Filter change Reminder Select an interval between Disable default and 365 days to remind you that the HVAC system requires maintenance This feature allows you to set time intervals between changing and or cleaning the HVAC filter If ...

Page 54: ...der an alert is generated after 30 runtime days have elapsed from this date Set Date and Time Displays the date and time of the web browser Unaltered this date and time can be assigned to the thermostat by first checking the Set Thermostat Time check box and clicking Submit If a different date and time is desired you can change the date and time field prior to checking the Set Thermostat Time chec...

Page 55: ...3 0 3 19 Part No 600 01000 200 Rev 2 Setback Schedules Page The Professional Series thermostat supports a set of scheduling options that you can configure through the TMI to create customized heating cooling or fan schedules Figure 3 5 shows an example of the Setback Schedules page Figure 3 5 Setback Schedules Page ...

Page 56: ...air flow The TMI supports the following three Day Classes shown in Figure 3 6 Figure 3 6 Day Class Scheduling Each Day Class supports the following four non overlapping periods of time in which you can independently specify heat cool and fan settings Morning pre business hours Day business hours Evening after hours Night unoccupied hours Defines days in which the user is occupying the property for...

Page 57: ... three day classes to each day of the week for every week of the year The TMI applies this weekly template to every week in each month that is visible in the Calendar View table at the bottom of the Setback Schedules Page page 3 19 To edit the Default Weekly Schedule click Edit Weekly Schedule and continue with Default Weekly Schedule page 3 24 Calendar View The Calendar View table displays the da...

Page 58: ...le Pages From the Occupied Unoccupied or Other Class Schedule page you can assign both heat and cool temperature settings as well as fan schedule settings in each of the four schedule Periods Figure 3 7 shows an example of the Occupied Day Class Schedule page The Unoccupied and Other Schedule pages displays fields similar to those in Figure 3 7 Figure 3 7 NT150e h Occupied Unoccupied or Other Day ...

Page 59: ... schedule begins on the hour and advances for the duration specified Note that within the hour of each Period but outside the schedule interval the fan reverts to AUTO mode to ensure proper operation for either a heating or cooling call to the HVAC system Select one of the following options Disable Off default No fan operation scheduled within this Period On Fan is forced On for the entire hour fo...

Page 60: ...asses see Figure 3 6 on page 3 20 to each of the seven days of the week Figure 3 8 Default Weekly Schedule Page Use Table 3 4 to assign Day Classes to each day of the week Table 3 4 Default Weekly Schedule Field Descriptions Field Description Day Displays the seven days of the week Class Select one of three Day Classes for each day of the week Occupied Occupied Day Class Unoccupied Unoccupied Day ...

Page 61: ...every Monday through Friday as Occupied and you want to schedule a national holiday or a company shutdown go to the Schedule Special Days page 3 25 and configure the day s or week s as Other schedule This allows you to designate certain days weeks or months to be different from the default schedule Special Days entries are organized as rows in the Special Days table The TMI supports 15 Special Day...

Page 62: ... December and requires a single Special Days entry in the table You can enter this information in the Special Days table using either of the following methods Click directly on the date on the Calendar View See Figure 3 5 on page 3 19 Figure 3 10 on page 3 27 appears and the TMI automatically populates all the fields in the row except the Day Class setting One day is the default duration but you c...

Page 63: ...Beta Draft Confidential Setback Schedules Page Professional Series Network Thermostat Configuration Guide Release 3 0 3 27 Part No 600 01000 200 Rev 2 Figure 3 10 Special Days Table Page Example 1 ...

Page 64: ...e thermostat schedule from the December 23 2007 through December 29 2007 Figure 3 11 Special Days Table Page Example 2 For example to add a week long holiday period 1 Click Edit Special Days from Figure 3 5 on page 3 19 Figure 3 11 appears 2 Enter all fields The Day Class field is updated to Other 3 Click Submit The Setback Schedules Page page 3 19 appears Note To remove any of the Special Days yo...

Page 65: ...ules Page Professional Series Network Thermostat Configuration Guide Release 3 0 3 29 Part No 600 01000 200 Rev 2 The Setback Schedules Page now displays the two Special Days entries in the Calendar View Figure 3 12 Setback Schedules Page ...

Page 66: ...01000 200 Rev 2 CHAPTER 3 Configuring the Thermostat Using the TMI Network Settings Page From the Network Settings Page you can configure the appropriate network parameters specific to your local network such as configuring the Syslog server address to receive messages and alerts Figure 3 13 Network Settings Page ...

Page 67: ...ent IP address assignment for remote access or for simplified local access IP Address Displays the unique Internet Protocol address either assigned statically or by DHCP See IP Address Method You must click Submit after changing this parameter to invoke a software reset to set the new value A B C D Four field standard dot notation for IP address designation Subnet Mask Enter the IP subnet on which...

Page 68: ...Port Enter the IP port number of the HTTP server within the thermostat This field defines the IP port number assigned to the web server internal to the thermostat for remote access Note that if you are trying to access the thermostat s Web pages then you must be able to access the thermostat on this port You must click Submit after changing this parameter to invoke a software reset to set the new ...

Page 69: ...r Defined Access Filter is selected this field displays the unique Internet Protocol address required in conjunction with the Network Mask to allow network accesses A B C D Four field standard dot notation for IP address designation Network Mask If the User Defined Access Filter is selected this field displays the network mask required in conjunction with the Network Address to allow network acces...

Page 70: ...om the thermostat 1 5 30 60 The amount of time in minutes between successive Syslog messages sent by the thermostat after an error event and before the error event is cleared Syslog alarm alert messages are sent to the Syslog server every minute until the alarm alert condition is cleared on the thermostat Alarm alert messages are sent with a Local7 Facility Code and with a severity level of Alert ...

Page 71: ...s Page The Advanced Settings page enables you to customize the thermostat by selecting the HVAC type and setting heating and cooling parameters How you configure your thermostat depends on the type of HVAC system you have Heat Pump or Fuel Burner Figure 3 14 shows the Advanced Settings page for a Heat Pump HVAC system Figure 3 14 Advance Settings Page Heat Pump HVAC ...

Page 72: ...work Thermostat Configuration Guide Release 3 0 Part No 600 01000 200 Rev 2 CHAPTER 3 Configuring the Thermostat Using the TMI Figure 3 15 shows the Advanced Settings page for a Fuel Burner HVAC system Figure 3 15 Advanced Settings Page Fuel Burner HVAC ...

Page 73: ...VAC Mode must be set to Off prior to selecting the opposite setting See the Status Control Page page 3 9 If Your HVAC System is a Fuel Burner Heat Control Select the HVAC control for this thermostat This parameter describes the thermostat capability to control a single stage or dual stage heating system The thermostat can also be disabled from controlling a heating system and instead operate as a ...

Page 74: ...s include 0 2 3 4 5 6 F 0 1 0 1 5 2 0 2 5 3 0 C Second stage A C temperature offset from first stage A C set point temperature If Your HVAC System is a Heat Pump Reverse Valve Polarity Enables you to control the direction of the heating and cooling modes O Indicates that the heat pump normally runs in heat mode and when the reversing valve is activated then the heat pump will run in cooling mode B...

Page 75: ...stat s capability to control a heat pump system The thermostat can also be disabled from controlling a cooling system and instead operate as a heat only thermostat See Heat Control page 3 37 Disable Specifies that there is no cooling system present Heat only thermostat 2C Enables the heat pump as a standard dual stage cooling system 1C Enables the heat pump as a standard single stage cooling syste...

Page 76: ...ycles in heat pump applications This parameter ensures a safe heat pump compressor delay or off time guaranteed between cycles This parameter may also be used in fuel burner mode whereby this parameter ensures a safe A C compressor delay or off time guaranteed between A C cycles 0 Enables the cooling system to cycle immediately upon completion of the previous cycle This is a diagnostic feature and...

Page 77: ...ntervals In this example a subsequent call for cool after the initial cool call in a 20 minute interval is deferred until the start of the next 20 minute interval This feature can be defeated by the user if changes are made to override the setpoint settings either at the thermostat or via the TMI This feature only applies to scheduled temperature settings Disable This feature is disabled and unlim...

Page 78: ... the trigger level or until a heat setpoint is encountered When a heat setpoint is encountered the HVAC heating cycle is invoked After the heat setpoint has been satisfied the HVAC cooling cycle to satisfy humidity requirements is delayed for 5 minutes Humidity control is intended for moderate moisture control High humidity environments should also include secondary dehumidification equipment Disa...

Page 79: ... Disables the External Relay Trigger Above Humidity Upper limit above which excessive relative humidity activates the External Relay See Threshold NT150e h and NT160e h only page 3 44 When the relative humidity falls 5 below the trigger point the External Relay is deactivated Below Humidity Lower limit below which lower relative humidity activates the External Relay See Threshold NT150e h and NT16...

Page 80: ...When the temperature falls below trigger setpoint minus the setpoint differential the relay is deactivated 30 F 34 C to 200 F 95 C For Below temperature limits When the average temperature falls below the trigger point the External Relay is activated When the temperature rises above the trigger setpoint plus the setpoint differential the relay is deactivated Activate Polarity NT150e h and NT160e h...

Page 81: ...etting Performs a software reset on the thermostat All current settings are maintained after the execution of this reset This reset is performed to return the thermostat to a known state after abnormal behavior No Action default A software reset is NOT performed after clicking Submit Software Reset Invokes a software reset after clicking Submit Table 3 6 Advanced Settings Fields HVAC Fuel Burner F...

Page 82: ...mostat Using the TMI Sensor Settings Page From the Sensor Settings page you can add external thermal sensors and configure zone temperature thermal averaging of the Local or the two Remote Sensors Figure 3 16 Sensor Settings Page Note This page is not available on the NT100e h Network Thermostat because the NT100e h does not support external thermal sensors ...

Page 83: ...pates in the algebraic averaging The Zone Temperature now reflects the average temperature of the averaged measurements Disable The thermostat internal sensor is excluded from the thermal averaging calculations Sensor Correction Selects a value to adjust the sensor for calibration 5 F 2 8 C through 5 F 2 8 C The default is 0 Remote Sensor 1 and 2 Name Displays the Name 15 characters for the extern...

Page 84: ...ermal averaging is disabled Enable Remote Sensor 1 2 is included in the thermal averaging calculations The Zone temperature now reflects the average temperature of the averaged measurements Sensor Correction Indicate the calibration or temperature offset compensation for this remote thermal sensor Offset adjustments are added or subtracted from the actual temperature read from this sensor and disp...

Page 85: ...the Proliphix Web Server IP address for processing and subsequent transmission as an e mail Remote Server Configuration You can access the Professional Series thermostat remotely from anywhere in the world using a web browser By default Proliphix thermostats intercommunicate with the Proliphix Web Server to provide this capability If the Proliphix Web Server is not used a private server may be use...

Page 86: ... enabled to participate with a Remote Server either the Proliphix Remote Management Server See the Proliphix Installer Remote Management Guide or a private server to provide remote access capability Remote Server Configuration Server Address The IP address of the Remote Server either the Proliphix Remote Management Server or a private server which supports remote access This field is pre configure...

Page 87: ...mmunication between the thermostat and the remote server If there is a good communication connection between the thermostat and the remote server the server deems that the thermostat is reachable and accessible by a user through the Internet mm dd yyyy Date of last successful communication with the remote server Default status is No Attempt hh mm ss Time since last successful communication with th...

Page 88: ...bled on the Remote Access Page page 3 49 the Remote Discovery Status Page page 3 52 appears This page displays a brief synopsis of the state of the thermostat and initiates the discovery process with the remote web server e g Proliphix web server on the Proliphix Web Site Click Back to Remote Access Settings to return to the Remote Access Page page 3 49 and view a completion status of the discover...

Page 89: ... 3 0 3 53 Part No 600 01000 200 Rev 2 Installer Info Page The Installer Information Page is included within the administrator pages specific to those responsible for the installation and management of the thermostat This page contains contact information for the installer Figure 3 19 Installer Info rmation Page ...

Page 90: ...e h and NT160e h only provide a minute accurate duration activity for all relays Each counter directly accumulates the number of minutes each relay has been active Only the Admin istrator account can reset the current value for each of the counters to zero To reset the Fan Usage counter click the Filter Replaced check box on the General Settings Page page 3 14 Figure 3 20 Usage Counters Page Note ...

Page 91: ...field Cool2 Displays the second stage Cool2 relay minute activity counter The Admin account user can reset this field by setting Reset Counters in the Last Counter Reset field Fan Displays the Fan relay minute activity counter Can be reset only by resetting the Filter Reminder Alarm setting on the General Settings Page page 3 14 External Relay NT150e h and NT160e h only Displays the External Relay...

Page 92: ...APTER 3 Configuring the Thermostat Using the TMI Password Settings Page You can access additional installer specific pages after successfully logging in as an administrator As a user you may change your password As an administrator you may also change the administrator and or user passwords Figure 3 21 Admin Password Settings Page ...

Page 93: ...Schedules Page page 3 19 Table 3 10 Admin Password Settings Field Descriptions Field Description Admin Password New Password Enter an alpha numeric password for the Administrator admin account The password is case sensitive and limited to 15 alpha numeric characters The default password is admin Confirm Password Re enter your password from the New Password field User Password New Password Enter an...

Page 94: ...re 3 22 Figure 3 22 User Password Settings Page Use Table 3 11 to complete the Admin Settings User Password page fields Table 3 11 Admin Settings User Password Field Descriptions Field Description User Password New Password Enter an alpha numeric password for the User account The password is case sensitive and limited to 15 alpha numeric characters The default password is admin Confirm Password Re...

Page 95: ...et may be necessary to bring the thermostat back into proper operation Software Reset A software reset reboots the network processor and retains the programming and thermostat setback schedules To perform a software reset at the thermostat 1 From the Status Control Screen page 2 10 select Thermostat Control Screen page 2 11 2 Press and hold Reset for longer than 3 seconds see Figure 2 9 on page 2 ...

Page 96: ...ee the Proliphix Thermostat Installation Guide 2 Attach the top of the cover to the top of the base as a hinge 3 Press and hold the middle button of thermostat while closing the cover into the base Do not release the button until the LCD characters appear Caution Performing a factory reset clears the setback scheduling and other programmed parameters These settings can not be recovered after a res...

Page 97: ... using the TMI 3 1 Cool setpoint temperature 2 5 D Day class 3 20 Default host name 3 3 Default weekly schedule 3 21 3 24 Device name zone name 3 3 DHCP See Dynamic Host Configuration Protocol 3 2 Down arrow 2 2 Dynamic Host Configuration Protocol 3 2 E External thermal sensors settings 3 47 F Factory reset 4 2 Filter set change reminder 3 17 Firewall settings 3 32 Fuel burner settings for 3 37 G ...

Page 98: ... management 3 4 Remote sensor current temperature 3 10 Right button 2 2 S Secondary screen 2 3 Security 3 32 Sensor settings page 3 46 Sensor status screen described 2 9 Setback schedules page 3 29 Software reset 4 1 Special days 3 25 Status control page 3 7 3 9 Status control screen described 2 10 Subnet mask 3 31 T TDI See Thermostat Device Interface 1 2 Temperature hold 2 5 Thermostat accessing...

Page 99: ...x Professional Series Network Thermostat Configuration Guide Release 3 0 Index 3 Part No 600 01000 200 Rev 2 U Unoccupied day class described 3 20 settings 3 22 Up arrow 2 2 Usage counters 3 54 V VPN 3 4 W Web port identifier 3 3 ...

Page 100: ...Index 4 Professional Series Network Thermostat Configuration Guide Release 3 0 Part No 600 01000 200 Rev 2 Index ...

Reviews: