40424 - 2nd Float Offset
Used to calibrate bottom float reading (-10,364 - 10,364 mm). Differences in fluid specific gravity can change
the level at which a float rests in the liquid. Use this parameter to match probe reading to confirmed liquid
level.
40423 - 1st Float Offset
Used to calibrate top float reading (-10,364 - 10,364 mm). Differences in fluid specific gravity can change the
level at which a float rests in the liquid. Use this parameter to match probe reading to confirmed liquid level.
40425 - Gain Offset (Factory Calibrated)
Used to move the centerline of the float response signal to optimize signal strength (0 - 255).
•
APG Modbus Register Lists for MPX-E/R2 and MPX-E/R3
Input Registers (0x04)
Register
Returned Data
30299
Model Type
30300
Top Distance (raw float reading, in mm, unsigned)
30301
Bottom Distance (raw float reading, in mm, unsigned)
30302
Temperature Reading (in
0
C, signed)
30303-30304
Top Calculated (level, volume, etc., in selected Units)
30305-30306
Bottom Calculated (level, volume, etc., in selected Units)
30307
Version
NOTE
: Input Register values for MPX-E/R2 and MPX-E/R3 are only visible while pro-
gramming via the RST-4100.
NOTE
: Input Registers 30300 and 30301 also display Loss of Signal error codes. See
Fail Safe (Holding Register 40411).